TABLE 7. Outdoor Control 7-Segment Display Alert Codes and Inverter LED Flash Codes
NOTE – System fault and lockout codes take precedence over system status codes (cooling, heating operating percentages or defrost/dehumidifi-
cation). Only the latest active fault or lockout codes are displayed (if present). If no fault or lockout codes are active, then system status codes are
displayed. Alert codes are also displayed on the S30/S40 thermostat.
Inverter LED Flash Code
Alert
Inverter
(number of flashes)
Codes
Code
Red LED
E426
N/A
N/A
E427
21
2 flashes
E428
22
2 flashes
E429
23
2 flashes
E430
26
2 flashes
E431
27
2 flashes
E432
28
2 flashes
Priority
Green LED
N/A
Critical
Excessive inverter alarms
The inverter has detected a DC peak fault condition. If condition (55A or higher) is detected, outdoor
unit compressor and fan stop. Anti-short cycle is initiated. If peak current (55A or higher) occurs 10
Moderate
times within an hour, system is locked out. Indicates high pressure, condenser fan failure, locked
1 flash
/ Critical
compressor rotor or overcharge. To clear, disconnect power to the indoor unit (24VAC power
source to the outdoor control) which will power off the outdoor control and will open the outdoor unit
contactor, which interrupts power to the inverter and then re-apply power..
Moderate
The inverter has detected a high
2 flashes
/ Critical
main input current condition.
On a call for compressor
operation, if DC link power
in inverter does not rise
above 180 VDC for 2 and 3
ton models, 250 VDC for 4
and 5 ton models, within 30
seconds, the control will display
Moderate
3 flashes
a moderate code. If condition
/ Critical
is detected, outdoor unit will
stop (Compressor and fan).
Antishort cycles is initiated. If
condition occurs 10 times within
a 60 minute rolling time period,
system will lock out and display
a critical code.
Moderate
6 flashes
Compressor start failure
/ Critical
Error occurs when PFC detects
an over-current condition of
100A, the control will display a
moderate code. If condition is
detected, outdoor unit will stop
(Compressor and fan). Anti-
Moderate
7 flashes
short cycle is initiated. Inverter
/ Critical
is unavailable to communicate
with the outdoor control for 3
minutes. If condition occurs 10
times within a 60 minute rolling
time period, system will lock out
and display a critical code.
Moderate
The inverter has detected a DC
8 flashes
/ Critical
link high voltage condition
Alarm Description
After ten faults within one hour, control is locked out, indicating
poor system operation. Review history of alarms to resolve system
setup. Check condenser fan motor, TXV, indoor unit blower motor,
over-charge, undercharge, or clogged refrigerant filter.
To clear, disconnect power to the indoor unit (24VAC power source
to the outdoor control) which will power off the outdoor control and
will open the outdoor unit contactor, which interrupts power to the
inverter and then re-apply power. Inverter alarms 12 to 14 and 53
do not count toward this lock out condition.
If condition is detected, is detected, outdoor unit compressor and
fan stop. Antishort cycle is initiated. If condition occurs 5 times
within an hour, system is locked out. Indicates high pressure,
condenser fan failure or overcharge.
To clear, disconnect power to the indoor unit (24VAC power source
to the outdoor control) which will power off the outdoor control and
will open the outdoor unit contactor, which interrupts power to the
inverter and then re-apply power.
Issues:
(1) If DC link power in inverter does not rise above 180 VDC for 2-
and 3-ton models, 250 VDC for 4- and 5-ton models, within 30
seconds, the outdoor control will display a moderate code.
(2) Capacitors on inverter do not properly charge.
Corrective Actions:
(1) Check for proper main power to outdoor unit and for any loose
electrical connections.
If condition is detected, outdoor unit compressor and fan stop.
Antishort cycle is initiated. If condition occurs 10 times within an
hour, system is locked out.
Indicates poor connection at compressor harness, improper
winding resistance, locked compressor rotor, or flooded
compressor.
To clear, disconnect power to the indoor unit (24VAC power source
to the outdoor control) which will power off the outdoor control and
will open the outdoor unit contactor, which interrupts power to the
inverter and then re-apply power.
Issues:
(1) Indicates power interruption, brownout, poor electrical
connection or loose inverter input wire.
(2) System testing was set up and code was generated when the
reversing valve is de-energized coming out of defrost (code
appears with or without 30 compressor delay).
Corrective Actions:
(1) Check for proper main power to outdoor unit and for any loose
electrical connections.
(2) To clear, disconnect power to the indoor unit (24VAC power
source to the outdoor control) which will power off the outdoor
control and will open the outdoor unit contactor, which
interrupts power to the inverter and then re-apply power.
Error occurs when the DC link capacitor voltage is greater than
480VDC. If condition is detected, outdoor unit compressor and fan
stop. Anti-short cycle is initiated. If condition occurs 10 times within
an hour, system is locked out. System stops.
To clear, disconnect power to the indoor unit (24VAC power source
to the outdoor control) which will power off the outdoor control and
will open the outdoor unit contactor, which interrupts power to the
inverter and then re-apply power.
Page 37
Possible Causes and Clearing Alarm