Ptcr Diagnosis - Scotsman CME256 Product Manual

Autoiq cubers
Hide thumbs Also See for CME256:
Table of Contents

Advertisement

CME256, 506, 656, 806: AutoIQ™ Cubers

PTCR Diagnosis

The CME256, CME506, CME656 and CME806
"D" series cubers use a PTCR (Positive
Temperature Coefficient Resistor) in place of a
conventional start relay and start capacitor.
Power from the contactor connects to the
PTCR and to the Run Capacitor.
A wire connects the other terminal of the
PTCR to the compressor's Start winding.
Another wire connects the run capacitor to
the start winding.
A parallel circuit connects power from the
contactor to the Run winding of the
compressor.
A PTCR changes resistance sharply when its
temperature changes. When the PTCR is cold, it
connects full current to the compressor's start
winding. After a very short time the PTCR heats up
and shuts off the current flow. Under normal
operation, the PTCR's case is at about 180
At that temperature the PTCR has very high
resistance and will not allow current flow. It must
o
cool down to 120
F. before current will pass
through it again.
Diagnosis:
1. Disconnect electrical power.
2. Check if the PTCR is cool enough to handle
safely. If not, wait 5 minutes for it to cool off.
3. Disconnect both leads to the PTCR and
measure its resistance with an ohmmeter. If the
PTCR reads less than 22 ohms or more than 40
ohms, replace it.
o
F.
January 2002
Page 26