Installation space
Keep the space necessary for installation and service.
REQUIREMENT
1. Before installation of the unit, mount the
accessories sold separately (Drain-up kit, etc.)
to the unit. In addition to the air inlet panel, set
also the check port at the side face.
2. The check port should be 600 × 600mm.
Installation under atmosphere of the high humidity
Although it has been confirmed that no trouble occurs on the unit, there is a fear of drip of the water if operation
under high humidity condition continues.
In some cases including the rainy season, especially inside of the ceiling may become high-humidity atmosphere
(dew-point temperature: 23°C or higher).
1. Installation to inside of the ceiling with tiles on the roof
2. Installation to inside of the ceiling with slated roof
3. Installation to a place where inside of the ceiling is used for pathway to intake the outside air
• In the above cases, additionally attach the thermal insulator
(Glass wool, etc.) to all positions of the air conditioner,
which come to contact with the high-humidity atmosphere.
In this case, arrange the side plate (Service plate) so that it
is easily removed.
• Apply also a sufficient thermal insulation to the duct and
connecting part of the duct.
3

INSTALLATION OF INDOOR UNIT

Install the air conditioner certainly to sufficiently withstand the weight.
If the strength is insufficient, the unit may fall down resulting in human injury.
Perform a specified installation work to guard against strong wind or earthquake.
An incomplete installation can cause accidents by the units falling and dropping.
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be
sure to use buffering cloth, etc. to not damage the unit.
• To move the indoor unit, hold the hooking metals (4 positions) only.
Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or resin parts, etc.).
• Carry the package by two or more persons, and do not bundle it with PP band at positions other than specified.
Service space
Electric parts box
Service plate
WARNING
REQUIREMENT
4
Distance from building
600 × 600mm
Check port
Duct
Check port