INSTALLATION DIAGRAM OF INDOOR UNIT

Batteries
5
3
Filter
Flat head
7
wood screw
Wireless
2
remote control

Optional Installation Parts

Part
Parts name
code
Refrigerant piping
A
Liquid side : Ø6.35 mm
Gas side
: Ø9.52 mm
Pipe insulating material
B
(polyethylene foam, 6 mm thick)
C
Putty, PVC tapes
Refrigerant piping
must be protected from
physical damage.
Install a plastic cover or
equivalent.
Remote control
4
holder
Q'ty
One
each
1
One
each
Hook
1
Installation
plate
Shield pipe
6
For the rear left, bottom left and left piping
Wall
Cut out a piece of SPACER from indoor
unit packaging box, roll it and insert
between the indoor unit and wall to tilt
the indoor unit for better operation.
The auxiliary piping can be connected to
the left, rear left, rear right, right, bottom
right or bottom left.
Right
Rear
right
Bottom
Rear
left
right
Bottom left
Do not allow the drain hose to get slack.
Cut the piping
hole sloped
slightly.
Make sure to run the drain hose sloped
downward.
Insulate the refrigerant pipes separately
with insulation, not together.
6 mm thick heat resisting
polyethylene foam
Left