VENTING INSTALLATION
Continued
Straight/Adjustable
Pipe 18" Max.
Horizontal Square
Termination
45°
Elbow
Wall
Firestop
Corner Installation
vertical (v)
5
/
" Min.
1
Figure 19 - Horizontal Termination
Configuration for Corner Installation
(Model (V)CD36R)
90°
Wall
Elbow
Firestop
Figure 20 - Horizontal Termination
Configuration Round Termination
(Model (V)CD36T)
GROUND FLOOR INSTALLATION
Recommended Applications for Rear Vent
Model (V)CD36T:
• Installation using cabinet surrounds
• Through wall using round or square termi-
nation (up to 24" horizontal pipe)
• Corner installation (Using one 90° elbow
and a maximum of 24" of horizontal pipe)
116035-01J
Horizontal
Square
Termination
Horizontal (H)
24" Max
Exterior
Portion of Wall
Square
Firestop (Round
Termination
Termination Only)
Horizontal
Round
Termination
www.desatech.com
Straight/
Adjustable
Pipe 24" Max.
Wall
V
Firestop
H
Corner Installation
vertical (v)
Horizontal (H)
45
/
" Min.
3
/
" Max
1
1
Figure 21 - Horizontal Termination
Configuration For Corner Installation
Using One 90° Elbow (Model (V)CD36T)
Not to Exceed
(H) Limits
Wall
Firestop
Required
vertical (v)
vertical (v)
vertical Pipe
45
/
"
None
1
57
/
" Min.
1 ft.
1
4
69
/
" Min.
2 ft.
1
4
81
/
" Min.
3 ft.
1
94" Min.
4 ft.
106" Min.
5 ft.
159" Min.
9 ft.
Figure 22 - Horizontal Termination
Configuration with Vertical Rise and One
90° Elbow (Model (V)CD36T)
90°
Elbow
90° Elbow
As
Required
for (V),
See Chart
for Pipe
Section
Required
Allowable
Horizontal (H)
26" Max.
30" Max.
74" Max.
98" Max.
122" Max.
146" Max.
20' Max.
15