Preventative Maintenance Checks and Services (PMCS)
Date Completed
Name
1.
Conduct a visual inspection of the system for chaffing or loose hose(s), dirt,
corrosion or damage.
2.
Check the Air Cylinder for normal operating pressure (1800-2200 psi).
a. Ensure System is depressurized.
b. Disconnect Air Cylinders and pull out of unit.
c. Connect Air Cylinder Pressure Check Gauge.
d. Open Air Cylinder and check for normal operating pressure. (1800-
2200psi)
e. Close Air Cylinder and slowly disconnect Pressure Check Gauge allowing
for pressure bleed off.
f. If the Air Cylinder pressure is below 1500 psi remove, recharge and
replace the Air Cylinder.
The Air Cylinder should normally be left in the closed position.
______ 3.
Check the Premix Tank Level
a. Disconnect fill tower Cap check liquid level.
b. Fill up the Premix Tank if low.
_______ 4.
Check the tire condition.
Note any other Problems: