5-4.
Servicing In Cold or Freezing Conditions
Fill the Premix Tank with FIREBULL® Fluorine Free Foam solution whenever
temperatures are below 32 degrees Fahrenheit. FIREBULL® should be used in the
concentrate form in cold or freezing temperature conditions. FIREBULL® Fluorine Free
Foam is a solution made by Enforcer One, LLC. The Pre-Mix solution is already mixed,
this means Water and Foam, no need for mixing onsite. Maintenance personal should
open the Pre-Mix bucket and fill the Enforcer unit full of the Pre-Mix solution.
5-5.
Scheduled Maintenance Interval Recommendations
Component
Air Cylinder
Cleaning
Air Regulator
Premix Tank
&
Discharge Hose
Foam Solution
5-6.
Unscheduled Maintenance
Unscheduled maintenance will need to be performed as required.
5-7.
Trouble Shooting the System
Users should contact Enforcer One if malfunctions cannot be corrected after employing
good troubleshooting practices. Use the matrix on page 17 for assistance.
Enforcer One, LLC
Copyright 2020
Maintenance Activity and Recommended Interval
• Check pressure - every 6 months
• Visual inspection and certification – annually
• Hydrostatic testing – every 5 years
• Wash with soap and water – minimum annually
• Check Operation – every 2 years
• Pressurize and check for leaks – annually
• Hydrostatic testing should be completed every 5 years
• Follow Foam Manufacturer quality testing recommendations
FIREBULL® is a registered trademark of Enforcer One, LLC
Page 16