Location; Clearances; Rigging And Handling; Zz15 Unit Limitations - York ZZ Seies Installation Manual

Table of Contents

Advertisement

5835254-YIM-A-1119
Table 2: ZZ15 unit limitations
Size
(tons)
15
(15)
Excessive exposure of the furnace to contaminated
combustion air may result in equipment damage or
personal injury. Typical contaminates include the
following items:
• Permanent wave solution
• Chlorinated waxes and cleaners
• Chlorine based swimming pool chemicals
• Water softening chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (for example, perchloroethylene)
• Printing inks
• Paint removers
• Varnishes
• Hydrochloric acid
• Cements and glues
• Anti static fabric softeners for clothes dryers
• Masonry acid washing materials

Location

Use the following guidelines to select a suitable location for
these units:
• The unit is designed for outdoor installation only.
• Condenser coils must have an unlimited supply of air.
Where a choice of location is possible, position the unit on
either the north or east side of the building.
• Suitable for mounting on roof curb.
• For ground level installation, use a level concrete slab
with a minimum thickness of 4 inches. The length and
width must be at least 6 inches greater than the unit base
rails. Do not tie the slab to the building foundation.
• Roof structures must be able to support the weight of the
unit and its options and accessories. The unit must be
installed on a solid, level roof curb or appropriate angle
iron frame.
• Maintain level tolerance to 1/2 inch across the entire width
and length of the unit.

Clearances

All units require particular clearances for proper operation and
service. The installer must make provisions for adequate
combustion and ventilation air in accordance with section 5.3 of
8
Model
Unit voltage
208/230-3-60
ZZ
460-3-60
Unit limitations
Applied voltage
Minimum
Maximum
187
432
Air for Combustion and Ventilation of the National Fuel Gas
Code, ANSI Z223.1 – latest edition (in the U.S.A.), or Sections
7.2, 7.3, or 7.4 of Gas Installation Codes, CSA-B149.1 (in
Canada) - latest edition, and/or applicable provisions of the
local building codes. See Table 6 for the clearances required for
combustible construction, servicing, and proper unit operation.
Do not permit overhanging structures or shrubs to
obstruct the condenser air discharge outlet, combustion
air inlet, or vent outlets.

Rigging and handling

Exercise care when you move the unit. Do not remove any
packaging until the unit is near the place of installation. To rig
the unit, attach chain or cable slings to the lifting holes provided
in the base rails. You must use spreader bars across the top of
the unit. The spreader bars must have a length that exceeds
the largest dimension across the unit.
If a unit is installed on a roof curb other than a York
curb, you must apply gasketing to all surfaces that come
in contact with the unit underside.
Before lifting the unit, make sure that the unit weight is
distributed equally on the rigging cables so that it lifts
evenly.
Units may be moved or lifted with a forklift. Slotted openings in
the base rails are provided for this purpose.
THE LENGTH OF THE FORKS MUST BE A MINIMUM OF 60
INCHES.
All panels must be secured in place when the unit is
lifted.
The condenser coils must be protected from rigging
cable damage with plywood or other suitable material.
Outdoor DB temp
Maximum (°F)
252
125
504
125
®
Johnson Controls Ducted Systems