10-3. Indoor Unit
10-3-1. Installation Place
• A place which provides the spaces around the
indoor unit as shown in the diagram.
• A place where there are no obstacle near the air
inlet and outlet.
• A place which allows easy installation of the piping
to the outdoor unit.
• A place which allows the front panel to be opened.
• The indoor unit shall be installed as top of the indoor
unit comes to at least 2 m height. Also, it must be
avoided to put anything on the top of the indoor
unit.
CAUTION
• Direct sunlight on the indoor unit's wireless
receiver should be avoided.
• The microprocessor in the indoor unit should
not be too close to RF noise sources.
(For details, see the owner's manual.)
<Remote control>
A place where there are no obstacles such as a
•
curtain that may block the signal from the remote
control.
Do not install the remote control in a place
•
exposed to direct sunlight or close to a heating
source such as a stove.
Keep the remote control at least 1 m apart from
•
the nearest TV set or stereo equipment. (This is
necessary to prevent image disturbances or noise
interference.)
The location of the remote control should be
•
determined as shown below.
(Side view)
(Top view)
Remote
Reception
control
range
Fig. 10-3-1
Indoor unit
Remote
control
10-3-2. Cutting a Hole and Mounting
Installation Plate
<Cutting a hole>
When install the refrigerant pipes from the rear.
35
The center of the pipe hole is above
the arrow
1. After determining the pipe hole position on the
installation plate (
(∅ 65 mm) at a slight downward slant to the
outdoor side.
NOTE :
• When drilling a wall that contains a metal lath,
wire lath or metal plate, be sure to use a pipe hole
brim ring sold separately.
<Mounting the installation plate>
17 0
To unit out line
240mm
85
Hook
Pipe hole
Indoor unit
– 52 –
FILE NO. SVM-15009
23 mm
120
180
240
Pipe hole
∅65 mm
.
Fig. 10-3-2
ð
) drill the pipe hole
Anchor bolt holes
Hook
To unit out line
240mm
To unit out line
35mm
To unit out line
120mm
240
180
35
120
0
23
Hook
7
Mounting
Thread
screw
Weight
Fig. 10-3-3
Pipe hole (∅65 mm)
1
Installation plate