2. BEFORE INSTALLATION

Do not exert pressure on the resin parts when opening the unit or when moving it after opening.
Be sure to check the type of R32 refrigerant to be used before doing any work. (Using an incorrect
refrigerant will prevent normal operation of the unit.)
• When opening the unit or moving it after opening, be sure to lift it by holding on to the hanger bracket
without exerting any pressure on other parts, especially, drain piping, and other resin parts.
• Decide upon a line of transport.
• Leave the unit inside its packaging while moving, until reaching the installation site. Use a sling of soft
material, where unpacking is unavoidable or protective plates together with a rope when lifting, to avoid
damage or scratches to the unit.
• Refer to the installation manual of the outdoor unit for items not described in this manual.
• Do not dispose of any parts necessary for installation until the installation is complete.
• In order to protect the indoor unit from damage, use packing materials to protect the unit after carrying
until the installation starts.
• When selecting installation site, refer to the paper pattern.
• Do not use the unit in locations with high salt content in the air such as beachfront property, locations
where the voltage fluctuates such as factories, or in automobiles or marine vessels.
• Do not install accessories on the casing directiy. Drilling holes in the casing may damage electrical wires
and consequently cause fire.
I
2-1. ACCESSORIES
Check the following accessories are included with your unit.
(Do not dispose of any parts necessary for installation until the installation is completed.)
Name
(1) Drain hose
Quantity
1 pc.
Shape
Name
Quantity
1 each
(10) Large
0
(11) Medium-1
<? <?
Shape
(12) Medium-2
<?
2-2. OPTIONAL ACCESSORIES
• The optional decoration panel and remote controller are required for this indoor unit. (Refer to Table 1, 2)
(However, the remote controller is not required for the slave unit of a simultaneous operation system.)
• Check that the decoration panel is prepared.
(For the installation of the decoration panel, refer to the installation manual attached to the decoration
panel.)
(5) Paper pattern
(2) Metal clamp
for installation
1 pc.
1 pc.
Upper part
of packing
0
CU)
Sealing pad
1 pc.
1 pc.
(13) Small
(14)
(g)
(7) Washer
fixing plate
4 pcs.
Installation guide
1 pc.
(Other)
• Installation
manual
(15
•Operation
manual
3
Insulation for
fitting
1 each
(8) For gas
pipe
(9) For liquid
pipe

Advertisement