Quick Links

Service Literature
WARNING
To prevent serious injury or death:
1-
Lock-out/tag-out before performing maintenance.
2-
If system power is required (e.g., smoke detector main­
tenance), disable power to blower, remove fan belt
where applicable, and ensure all controllers and ther­
mostats are set to the "OFF" position before
performing maintenance.
3-
Always keep hands, hair, clothing, jewelry, tools, etc.,
away from moving part
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person­
al injury or loss of life. Installation and service must
be performed by a licensed professional HVAC in­
staller or equivalent, service agency, or the gas sup­
plier
The LHT commercial heat pump is available in 6.5, 7.5, 8.5,
10 and 12.5 ton capacities. The refrigerant systems utilize
two compressors, two reversing valves, two accumulators,
and other parts common to a heat pump. Electric heat oper­
ates in single or multiple stages depending on the kW input
size. 7.5kW through 60kW heat sections are available for
the LHT heat pump.
LHT078-150 units are equipped with variable-volume, di­
rect drive blowers. These units will provide supply air at
lower speeds when cooling demand is low and increase to
higher speeds when cooling demand is high. Refer to Sup­
ply Air Start-Up sections.
LHT units are designed to accept any of several different
energy management thermostat control systems with mini­
mum field wiring.
Information contained in this manual is intended for use by
qualified service technicians only. All specifications are
subject to change. Procedures outlined in this manual are
presented as a recommendation only and do not super­
sede or replace local or state codes.
If the unit must be lifted for service, rig unit by attaching four
cables to the holes located in the unit base rail (two holes at
each corner). Refer to the installation instructions for the
proper rigging technique.
100087
LHT HEAT PUMP SERIES
s.
CAUTION
As with any mechanical equipment, contact with
sharp sheet metal edges can result in personal in­
jury. Take care while handling this equipment and
wear gloves and protective clothing.
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at discon­
nect switch(es). Unit may have multiple
power supplies.
Table of Contents
Options / Accessories
Specifications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Data
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical \ Electric Heat Data
I Unit Components
II Placement and Installation
III Start Up
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IV System Service Checks
V Maintenance
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VI Accessories
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VII Wiring Diagrams
Page 1
LHT
6.5 / 7.5 / 8.5 /10 / 12.5
E
E
M
WARNING
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
2
5
7
10
16
28
28
29
31
32
37

Advertisement

loading

Summary of Contents for Lennox LHT Series

  • Page 1 Service Literature 6.5 / 7.5 / 8.5 /10 / 12.5 100087 LHT HEAT PUMP SERIES WARNING To prevent serious injury or death: Lock-out/tag-out before performing maintenance. If system power is required (e.g., smoke detector main­ tenance), disable power to blower, remove fan belt where applicable, and ensure all controllers and ther­...
  • Page 2 OPT IONS / A C C ESSORIES Unit Model No Catalog Item Description Number 078 092 102 122 150 COOLING SYSTEM 22H54 Condensate Drain Trap Copper 76W27 Drain Pan Overflow Switch 21Z07 BLOWER - SUPPLY AIR Blower Option DirectPlus™ Blower System with MSAV Factory ®...
  • Page 3 OPT IONS / A C C ESSORIES Unit Model No Catalog Item Description Number 078 092 102 122 150 ELECTRICAL Voltage 60 Hz 208/230V - 3 phase Factory 460V - 3 phase Factory 575V - 3 phase Factory Disconnect Switch 80 amp 54W56 150 amp...
  • Page 4 OPT IONS / A C C ESSORIES Unit Model No Catalog Item Description Number 078 092 102 122 150 ECONOMIZER High Performance Economizer (Approved for California Title 24 Building Standards / AMCA Class 1A Certified) High Performance Economizer 20U80 Downflow or Horizontal - Includes Outdoor Air Hood and Downflow Barometric Relief Dampers with Exhaust Hood Order Horizontal Barometric Relief Dampers separately Horizontal Barometric Relief Dampers...
  • Page 5 SP ECIF ICATIONS 6.5 TO N | 7 .5 TO N | 8.5 TO N General Data Nominal Tonnage 6.5 Ton 7.5 Ton 8.5 Ton Efficiency Type High High High Model Number LHT078H4E LHT092H4E LHT102H4E Blower Type DirectPlus™ DirectPlus™ DirectPlus™ ECM Direct Drive ECM Direct Drive ECM Direct Drive...
  • Page 6 SP ECIF ICATIONS 10 TO N | 1 2 . 5 TO N General Data Nominal Tonnage 10 Ton 12.5 Ton Efficiency Type High High Model Number LHT122H4E LHT150H4E Blower Type DirectPlus™ DirectPlus™ ECM Direct Drive ECM Direct Drive with MSAV with MSAV ®...
  • Page 7 BLO WER DATA BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE. FOR ALL UNITS ADD: 1 − Wet indoor coil air resistance of selected unit. 2 − Any factory installed options air resistance (heat section, Economizer, etc.) 3 −...
  • Page 8 BLO WER DATA FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE - in. w.g. Wet Indoor Coil Filters Return Air Electric Volume Economizer Adaptor Heat 078, 092 102, 122, 150 MERV 8 MERV 13 MERV 16 Plate 1750 0.04 0.04 0.03 0.05 0.01 0.03...
  • Page 9 BLO WER DATA CEILING DIFFUSERS AIR RESISTANCE - in. w.g. RTD11 Step-Down Diffuser FD11 Flush Air Volume 1 Side, 2 Ends All Ends & Sides Diffuser Unit Size 2 Ends Open Open Open 2400 0.21 0.18 0.15 0.14 2600 0.24 0.21 0.18 0.17...
  • Page 10 ELECTRIC AL/ELECTRIC H EAT DATA 6 .5 TO N Model No. LHT078H4E Voltage - 60Hz 208/230V-3ph 460V-3ph 575V-3ph Compressor 1 Rated Load Amps 12.9 (Non-Inverter) Locked Rotor Amps Compressor 2 Rated Load Amps (Non-Inverter) Locked Rotor Amps Outdoor Fan Full Load Amps (2 ECM) Motors (2) Power Exhaust Full Load Amps...
  • Page 11 ELECTRIC AL/ELECTRIC H EAT DATA 7 .5 TO N Model No. LHT092H4E Voltage - 60Hz 208/230V-3ph 460V-3ph 575V-3ph Compressor 1 Rated Load Amps 12.9 (Non-Inverter) Locked Rotor Amps Compressor 2 Rated Load Amps 13.7 (Non-Inverter) Locked Rotor Amps 83.1 Outdoor Fan Full Load Amps (2 ECM) Motors (2) Power Exhaust...
  • Page 12 ELECTR ICA L/ELECTRIC H EAT DATA 8.5 TO N Model No. LHT102H4E Voltage - 60Hz 208/230V-3ph 460V-3ph 575V-3ph Compressor 1 Rated Load Amps 12.9 (Non-Inverter) Locked Rotor Amps Compressor 2 Rated Load Amps (Non-Inverter) Locked Rotor Amps 38.9 Outdoor Fan Full Load Amps (2 ECM) Motors (2) Power Exhaust...
  • Page 13 ELECT RICA L/ELECTRIC H EAT DATA 10 TO N Model No. LHT122H4E Voltage - 60Hz 208/230V-3ph 460V-3ph 575V-3ph Compressor 1 Rated Load Amps 16.7 (Non-Inverter) Locked Rotor Amps 54.7 47.8 Compressor 2 Rated Load Amps 19.6 (Non-Inverter) Locked Rotor Amps 66.1 55.3 Outdoor Fan...
  • Page 14 ELECTR ICA L/ELECTRIC H EAT DATA 1 2 .5 TO N Model No. LHT150H4E Voltage - 60Hz 208/230V-3ph 460V-3ph 575V-3ph Compressor 1 Rated Load Amps 17.6 (Non-Inverter) Locked Rotor Amps 66.1 55.3 Compressor 2 Rated Load Amps 22.6 (Non-Inverter) Locked Rotor Amps 166.2 74.6 Outdoor Fan...
  • Page 15 LHT078-150 PARTS ARRANGEMENT OUTDOOR FANS BLOWER INDOOR (3 ON 122 & 150) (DIRECT DRIVE) COIL FILTERS (FOUR - 20 X 25 X 2”) ECONOMIZER (OPTIONAL) WIFI ANTENNA UNIT CONTROLLER WIRELESS BOARD OUTDOOR COIL ELECTRIC HEAT CONDENSATE COMPRESSORS (OPTIONAL) REVERSING DRAIN VALVE FIGURE 1 LHT078-150 CONTROL BOX...
  • Page 16 3-Transformer T1 The LHT unit parts arrangement are shown in figure 1. All All LHT series units use a single line voltage to 24VAC L1, L2, and L3 wiring is color coded; L1 is red, L2 is yellow, transformer mounted in the control box. Transformer sup­...
  • Page 17 PLUMBING COMPONENTS LHT078-102 Condenser Coil Evaporator Coil Reversing Valve Reversing Valve Compressor 2 Compressor 1 LHT122-150 Condenser Coil Evaporator Coil Reversing Valve Accumulators Compressor 1 Compressor 2 FIGURE 4 Page 17...
  • Page 18 B-Cooling Components NOTE-Refer to the wiring diagram section for specific unit operation. LHT units use independent cooling circuits consisting of separate compressors, outdoor coils and indoor coil (with 2 IMPORTANT separate stages). See figure 4. Units are equipped with two Some scroll compressors have an internal vacuum or three draw-through type condenser fans.
  • Page 19 3-Reversing Valve L1 and L2 frost). The switches are located on the expansion valve dis­ tributor assembly at the inlet to the outdoor coil. The switch A refrigerant reversing valve with a 24 volt solenoid coil is monitors the outdoor coil suction temperature to determine used to reverse refrigerant flow during unit operation in all when defrost is needed.
  • Page 20 LHT078, 092, 102, 122, 150 INDOOR COIL RT46, RT47 22J06 BLUE RT47 22J06 YELLOW RT46 DETAILS NOT TO SCALE FIGURE 5 Page 20...
  • Page 21 LHT078, 092, 102, 122, 150 OUTDOOR COIL RT48, RT49 22J08 BLUE RT49 22J08 YELLOW RT48 DETAILS NOT TO SCALE FIGURE 6 Page 21...
  • Page 22 C-Blower Compartment NOTE - Blower operation mode can also be initiated by the mobile service app. The blower compartment in all LHT092/150H units is locat­ Direct-drive motor may not immediately stop when power is ed between the indoor coil and the outdoor coil section. The interrupted to the Unit Controller.
  • Page 23 LOCATION OF STATIC PRESSURE READINGS INSTALLATIONS WITH DUCTWORK INSTALLATIONS WITH CEILING DIFFUSERS ROOFTOP UNIT ROOFTOP UNIT RETURN AIR READING LOCATION RETURN AIR READING RE­ RE­ LOCATION SUPPLY SUPPLY TURN TURN FIRST BRANCH OFF OF MAIN RUN MAIN DUCT RUN SUPPLY AIR SUPPLY AIR READING READING...
  • Page 24 Field Parameter Description Setting Note: Any changes to Smoke CFM setting must be adjusted before the other CFM settings. Use SETTINGS > RTU OP­ TIONS > EDIT PARAMETERS = 12 for EBM, 6 for ECM BLOWER SMOKE CFM % Percentage of RPM for blower smoke speed. SETUP >...
  • Page 25 D-Optional Electric Heat Components tors (K15, K16) are de‐energized. When the contactors are de‐energized, first stage and all subsequent Table 2 shows electric heat fuse ratings. See Options/Ac­ stages of heat are de‐energized. The thermostat is fac­ cessories section (see table of contents) for LHT to EHO tory set to open at 220_F + 6_F (104_C + 3.3_C) on a match-ups.
  • Page 26 ----- ELECTRIC HEAT CONTROL ASSEMBLY ELECTRIC HEAT CONTROL ASSEMBLY 1-Electric Heat Relay K9 All LHT series units with electric heat use an electric heat ELECTRIC HEAT relay K9. K9 is a N.O. DPDT pilot relay intended to electri­ CONTROL ASSEMBLY cally isolate the unit's 24V circuit from the electric heat 24V circuit.
  • Page 27 EHO 7.5, 15, 22.5, 30, 45, 60KW ELECTRIC HEAT SECTION PARTS ARRANGEMENT HEATING ELE­ SECONDARY MENTS LIMIT S20 HE1 - HE6 SECONDARY SECONDARY LIMIT S20 LIMIT S20 ELECTRIC HEAT VESTIBULE SECONDARY LIMIT S20 SECONDARY LIMIT S20 SECONDARY LIMIT S20 ELECTRIC HEAT THERMOSTAT PRIMARY ELECTRIC HEAT LIMIT...
  • Page 28 II-PLACEMENT AND INSTALLATION C-Cooling Start Up Make sure the unit is installed in accordance with the instal­ IMPORTANT lation instructions and all applicable codes. See acces­ sories section for conditions requiring use of the optional If unit is equipped with a crankcase heater. Make sure roof mounting frame (LARMF).
  • Page 29 IV- SYSTEMS SERVICE CHECKS REFRIGERANT STAGES - 078, 092, 102 WARNING (BOTH FANS ARE ENERGIZED IN LOW SPEED WITH A Y1 DEMAND AND HIGH SPEED WITH A Y2 DEMAND) Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly. Failure to follow this warning may result in personal OUTDOOR COIL OUTDOOR...
  • Page 30 TABLE 3 581118-01 TABLE 7 581122-01 LHT150 LHT078 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 Outdoor Outdoor Dis­ Dis­ Dis­ Dis­ Coil Coil Suction Suction charge Suction charge Suction charge charge Entering Entering +5 psig +5 psig +10 psig +5 psig +10 psig +5 psig...
  • Page 31 V-MAINTENANCE D-Indoor Coil Inspect and clean coil at beginning of each cooling and The unit should be inspected once a year by a qualified ser­ heating season. Clean using mild detergent or commercial vice technician. coil cleanser. Flush coil and condensate drain with water CAUTION taking care not to get insulation, filters and return air ducts wet.
  • Page 32 VI-ACCESSORIES TYPICAL FLASHING DETAIL The accessories section describes the application of most UNIT BASE of the optional accessories which can be factory or field in­ BOTTOM stalled to the LHT units. OPTIONAL ACCESSORIES sec­ tion (see table of contents) show specific size per unit. UNIT BASE RAIL A-C1CURB Mounting Frames FIBERGLASS...
  • Page 33 C1DAMP20B-1 MOTORIZED OUTDOOR AIR DAMPER MOTORIZED DAMPER COVER PANEL HORIZONTAL SUPPLY AIR OPENING COMPRESSOR HORIZONTAL SECTION RETURN AIR OPENING LOWER PANEL C1DAMP10B-1 MANUAL OUTDOOR AIR DAMPER COVER PANEL MANUAL DAMPER HORIZONTAL SUPPLY AIR OPENING COMPRESSOR HORIZONTAL SECTION RETURN AIR OPENING LOWER PANEL FIGURE 18 Page 33...
  • Page 34 ECONOMIZER ACCESSORY PANEL MULLION ECONOMIZER DIVIDER PANEL BOTTOM OF COMPRESSOR SECTION FLANGED RETURN AIR OPENING FIGURE 19 E-K1ECON20B Economizer Temperature offset is the default free cooling mode. NOTE - All free cooling modes of operation will modu­ (Field- or Factory-Installed) late dampers to 55_F (13_C) supply / discharge air.
  • Page 35 The dampers must be used any time an economizer and a power exhaust fan is applied to LHT series units. Barometric relief dampers allow exhaust air to be dis­ charged from the system when an economizer and/or pow­...
  • Page 36 NOTE-LHT heat pumps use standard heat cool type POWER EXHAUST FAN AND thermostats. Attempted use of heat pump-type ther­ BAROMETRIC EXHAUST DAMPER INSTALLATION mostats on LHT units will result in improper operation. J-Drain Pan Overflow Switch S149 (optional) GED GRAVITY EXHAUST The overflow switch is used to interrupt cooling operation DAMPERS...
  • Page 37 VII- WIRING DIAGRAMS / SEQUENCE OF OPERATION EHO-7.5, 15, 22.5, 30, 45 & 60kW Y VOLTAGE LHT SERIES UNITS Page 37...
  • Page 38 EHO-7.5, 15, 22.5, 30, 45 & 60kW G, J VOLTAGE LHT SERIES UNITS Page 38...
  • Page 39 Sequence of Operation -EHO 7.5, 15, 22.5, 30, 45, 60 kW - Y and G, J, M NOTE: This sequence of operation is for all Electric 4- N.O. contacts K15-1 close allowing the first bank of ele­ ments to be energized. Heat kW ratings Y through J voltages.
  • Page 40 ELECTRONIC OR ELECTROMECHANICAL THERMOSTAT − 0 1 A173 CTRL SMOKE DETECT J250 P250 P251 J251 J252 P252 P253 J253 FIRE ALARM CONTACT SUPPLIED BY OTHERS FROM IAQ WIRING DIAGRAM DI−1 P299 P387 J299 J387 MAIN CTRL J297 J298 P297 P298 J387 J298 J297 J299 IAQ+...
  • Page 41 LHT SERIES ECONOMIZER MS7110K RANGE 2−10 VDC NF24−SR AF24−SR RANGE 2−10 VDC P104 P105 RT16 J104 J105 P384 J384 MAIN CTRL Model: LC, LG, LH, LD Series RTU ACCS ACCS Economizer & Motorized OAD WI R I N G DI A GRAM F LOW...
  • Page 42 LHT078/150 Y Voltage With Higher SCCR DRNWR TO A3 ON GAS UNITS. REF A−SECT LOC CC01−02 RED−BLK RED−BLK 24VAC RT17 SHIELDED CABLE HPSW1 TWISTED PAIR HTSW1 DRNWR RED−BLK RED−BLK 24VAC ODF1 RT48 RT46 PWM2 P336 HTSW2 P337 RED−BLK RED−BLK 24VAC RT49 RT47 OPTIONAL IONIZER...
  • Page 43 LHT078-150 G Voltage With Higher SCCR DRNWR TO A3 ON GAS UNITS. REF A−SECT LOC CC01−02 RED−BLK RED−BLK 24VAC RT17 SHIELDED CABLE HPSW1 TWISTED PAIR HTSW1 DRNWR RED−BLK RED−BLK 24VAC ODF1 RT48 RT46 PWM2 P336 HTSW2 P337 RED−BLK 24VAC RED−BLK RT49 RT47 OPTIONAL IONIZER...
  • Page 44 LHT078-150 J Voltage With Higher SCCR DRNWR TO A3 ON GAS UNITS. REF A−SECT LOC CC01−02 RED−BLK RED−BLK 24VAC RT17 SHIELDED CABLE HPSW1 TWISTED PAIR HTSW1 DRNWR RED−BLK RED−BLK 24VAC ODF1 RT48 RT46 PWM2 P337 HTSW2 P336 RED−BLK RED−BLK 24VAC RT49 RT47 OPTIONAL IONIZER...
  • Page 45 SEQUENCE OF OPERATION LHT078-150 Power: 1. Line voltage through the S48 unit disconnect, TB2 terminal block, or CB10 circuit breaker energizes the T1 transformer. T1 provides 24VAC power to A55 Unit Controller which provides 24VAC to the unit cooling, heating and blower controls. 2.
  • Page 46 DIRECT DRIVE BLOWER SEQUENCE OF OPERATION / TROUBLESHOOTING Blower Operation: Line voltage is routed to B3 blower motor through TB2 terminal strip, TB13 terminal strip and J/P48 terminals 1, 2 and 3. B3 blower motor runs internal diagnostics to check for proper temperature, voltage, etc. (KL2-2 and -3). This process takes approximately 10 seconds.
  • Page 47 TABLE 10 DIRECT DRIVE BLOWER MOTOR TROUBLESHOOTING Failure Error Warning Reason Troubleshoot Check for obstruction keeping Locked Rotor • No changes in hall signals within 2000ms impeller from rotating Check for secondary airflow source in the system causing Warning, no error code set, Motor start not pos­ Braking Mode •...