Application Guide
GFK-2928C
Figure 18: GCG Assignments – Bus B
BUS.GCG_B.PRI_NUM The PROFINET Device Number for the Primary PLC Gateway module
BUS.GCG_B.SEC_NUM The PROFINET Device Number for the Secondary PLC Gateway
BUS.GCG_B.PSDA
BUS.GCG_B.GSDA

Dual Bus Parameters

Figure 19: Dual Bus Parameters
BUS.DEF_TO
BUS.DEF_HLS
BUS.DI_OFST
BUS.AI_OFST
Toolchest Components
attached to Bus B.
module attached to Bus B.
The PROFINET Status/Diagnostic bits for the Gateway module
attached to Bus B.
The Genius Device Status bits for the Gateway module attached to
Bus B.
The Default Timer Preset establishes the time interval (in
milliseconds) during which inputs are frozen while a device is
missing from Bus A AND from Bus B.
This parameter (a Boolean) determines the behavior of a missing
device:
If the parameter is set to 0, the inputs for that device will default to
OFF or 0 after the Default Timer expires.
If the parameter is set to 1, the inputs for that device will be frozen
in their last state until the device is reattached to either Bus A or Bus
B.
This applies to discrete inputs. It is the reference offset between a
discrete input configured on Bus A and the alternate address on Bus
B. For instance, a device configured at %I0001 on Bus A must be
configured at %I (1+DI_OFST) on Bus B. The offset must be in
multiples of 8 (i.e., on a byte boundary).
This applies to analog inputs. It is the reference offset between an
analog input configured on Bus A and the alternate address on Bus
Chapter 4
Oct 2019
16