Honeywell NOTIFIER UDS-3 User Manual, Installing And Operating Manual page 6

Table of Contents

Advertisement

Grounding
Grounding must be consistent with CEI and ISPELS rules and must have a resistance less than 10 Ohm
(measured at the grounding well without loads). Grounding cable must be connected to the control panel on
the CNA terminal board.
Protection grade
IP30
Weight
4.5 Kg
Terminals
CNA
1
Phase
2
Ground
3
Neutral
CNL1
L1-
1
2
L1-
3
L1+
4
L1+
CNL2
1
L2-
2
L2-
3
L2+
4
L2+
CNS
1
LIN+
2
GND
3
LIN-
CN0
Common outputs for zones 1 and 2
1
+ 24 USER
2
GND USER
3
NO-NC
4
C
5
NO-NC
6
C
7
NO-NC
8
C
9
NO-NC
10
C
11
NO-NC
12
C
PAGE - 5
NOTIFIER ITALIA
Inputs
230Vac power
Analog loop input for zone 1 discharge command
Analog loop input for zone 2 discharge command
Serial RS485 service connection
User power output
General fault relay
(1A contact - 24Vdc resistive)
Release in progress relay
(1A contact - 24Vdc resistive)
Emergency delay relay
(1A contact - 24Vdc resistive)
Only-manual discharge relay
(1A contact - 24Vdc resistive)
Emergency stop relay
(1A contact - 24Vdc resistive)
Installation and operating manual
Doc. M-205.1-UDS3N-ENG Rev A.1
1.25 A max.
JRL11 (Jumper for output type
selection NO/NC).
JRL13 (Jumper for output type
selection NO/NC).
JRL15 (Jumper for output type
selection NO/NC).
JRL16 (Jumper for output type
selection NO/NC).
JRL17 (Jumper for output type
selection NO/NC).
UDS-3