Extinguishing cycle flowchart
(1)
Release activation is performed if:
a.
both inputs from conventional control panel are
active;
b.
both pre-alarm inputs are given by the analog
control panel;
c.
manual activation input is active
(2)
Only if release delay time is different from 0
seconds
(3)
Release inhibition causes:
a.
emergency
extension
disablement means new delay initialization);
b.
damage to the transmission support towards
emergency
extension
causes immediate release if release delay has
finished);
c.
damage to the transmission support towards
emergency interruption device
causes immediate release if release delay has
finished);
d.
emergency interruption input active (inhibits
definitely release, after its deactivation a reset
must be given)
e.
Extinguishing output exclusion (if reset means
a new delay initialization)
PAGE - 34
NOTIFIER ITALIA
device
active
(its
device
(fault
reset
(fault reset
Installation and operating manual
Doc. M-205.1-UDS3N-ENG Rev A.1