Buzzer acoustic signalling is activated when one of the following happens:
1. in presence of the pre-activation signal, coming from terminal board or loop, buzzer acoustic signal is
silenced automatically if the pre-alarm cause is removed, bringing UDS-3 back to standby mode.
2. under active condition
3. under release condition if this is given by activation command coming from Flowmeter
4. under any fault condition
5. under emergency extension
RESET
It is possible to reset fault, activation and release condition through different keys under level 2 password.
Getting into this function it is possible to select:
zone 1 alarm/fault signals reset.
zone 2 alarm/fault signals reset.
system fault signals reset.
Selecting a zone allows resetting, if present, faults, activations and release conditions of the selected zone,
bringing it back to standby mode.
Selecting "System" command mains and common parts faults can be reset, practically all the errors shown
on the system faults screen.
SOUNDERS SILENCING
It allows disabling sounder output for each zone.
Getting into this function with level 2 password a specific zone can be selected.
EVACUATION: Activation command for Sounder output for each releasing zone. Getting into this function
through 2nd level password, you can select the zone whose sounder you want to start.