CONTROLLER

Central Controller Setting

Central Controller Setting
Only AC Smart 5 / ACP 5 or later must be used with the DOAS controller.
1. Confirm control wiring between DOAS controller and AC Smart 5 Channel 1 or ACP 5 Channel 6. (Wiring is 18 AWG, 2-conductor, twisted,
stranded, shielded, and must comply with all applicable local and national codes.)
Figure 62: DOAS Controller to Central Controller Connections.
2.
els):
• CAREL Modbus SubAddress = 18 (Hex)
• AC Smart or ACP Address = 12 (Hex)
Figure 63: Device I.D. Screen.