Electrical - LG ARND DCR4 Series Installation Manual

Split compact dedicated outdoor air system (doas)
Hide thumbs Also See for ARND DCR4 Series:
Table of Contents

Advertisement

GENERAL DATA

Electrical

Table 3: Split Compact DOAS Electrical Data
Model
Hz
ARND093DCR4
ARND153DCR4
60
ARND203DCR4
MCA : Minimum Circuit Ampacity.
12
Power Supply
Volts
Voltage Range
208-230
187-253
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
FLA
Phase
2.0
1
5.8
6.0
MOP : Maximum Overcurrent Protection: (Largest motor FLA x 2.25) + (Sum of other motor
FLA) rounded down to the nearest standard fuse size.
MCA
MOP
2.5
15
7.3
15
7.5
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Arnd093dcr4 arnd153dcr4 arnd203dcr4

Table of Contents