Mounting Dimensions - LG ARND DCR4 Series Installation Manual

Split compact dedicated outdoor air system (doas)
Hide thumbs Also See for ARND DCR4 Series:
Table of Contents

Advertisement

Mounting Dimensions

Table 15: Dimensions and Weights.
Overall Dimen-
Frame
Weight
sions (in.)
Code
(lbs.)
W
H
DC
364
75.1
21.7
Ductwork Configuration
When connecting ducts, insert a canvas duct between the main body and the duct.
• Use non-combustible duct components.
• Install sufficient insulation to prevent condensation forming on outlet duct flanges and outlet ducts.
The contractor is responsible for providing transitions to accommodate difference in sizing between the unit and the building ducts. Duct con-
nections to collar-type openings can be made with S-cleats or overlapping joints. Apply caulk around each duct connection. Failure to seal
duct connections can cause air leakage and system performance problems.
When an air duct which carries supply air or warm air passes through a combustible roof, a clearance of one (1) inch must be maintained between
the outside perimeter of ductwork and any combustible materials, per NFPA Standard 90A.
Table 16: Duct Connection Dimensions.
SA Outlet
Chassis
Code
L1
L2
DC
17.6
53.8
Mounting Dimensions
(in.)
D
M1
M2
M3
M4
45.1
77.2
37.3
1.1
6.8
OA Inlet
L3
L4
L5
L6
2.4
49
16.4
5.9
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
INSTALLATION
Figure 7: Split Compact DOAS Unit Mounting Dimensions.
Figure 8: Duct Connection Dimensions.
23