Potterton SIRIUS THREE FS 70 Installation Manual page 78

Floor-standing condensing gas boiler
Table of Contents

Advertisement

10 Settings
Parameter number
Heating
Heating
Heating
circuit 1
circuit 2
circuit 3
750
1050
1350
760
1060
1360
809
1109
1409
834
1134
1434
850
1150
1450
851
1151
1451
855
1155
1455
856
1156
1456
Tab.60
Temps / mode hot water menu
Parameter
Parameter
number
1600
Operating mode
1610
Hot water temp
setpoint
1612
Reduced temp
setpoint
78
Parameter
Description
Room influence
Influence of the room temperature and the
outside temperature on calculating the flow
temperature: ---%: Simple regulation in ac­
cordance with outside weather conditions:
1...99%: Regulation in accordance with out­
side weather conditions with room tempera­
ture influence.
100%: Regulation in accordance with the
room temperature only.
Room temp
Cuts the circulating pump if the room tempera­
limitation
ture exceeds the current set point + parameter
760, 1060, 1360.
Continuous pump
No : The heating circuit / boiler pump may be
operation
shut down during an accelerated decline in
temperature or when the room temperature
set point is reached.
Yes : The heating circuit / boiler pump also
continues to run during the accelerated de­
cline in temperature and when the room tem­
perature set point is reached.
Actuator running
Setting the stroke of the servomotor on the
time
mixing valve used
Floor curing
Controlled screed-drying function:
function
Off : The function is inoperative.
Curing/functional heating : Active for 7 days,
3 days at 25 °C and 4 days at 55 °C.
Curing heating : Active for 18 days, 6 days
from 25 °C to 55 °C increasing by 5 °C a
day, 6 days at 55 °C, 6 days from 55 °C to
25 °C diminishing by 5 °C a day.
Functional/curing heating : "Functional Heat­
ing" cycle first, and then "Ready for Occupa­
tion".
Manually : Regulation is based on the "Man­
ual Control Drying" set point.
Floor curing setp
The flow temperature set point of the "Manual"
manually
controlled drying function can be set separately
for each heating circuit.
Floor curing setp
Displays the current day of the controlled
current
screed-drying function. With '---' the function is
deactivated.
Days
Displays the current flow temperature set point
complete.current
of the controlled screed-drying function. With
'---' the function is deactivated.
Description
Off: Permanent running at the frost protection set point.
On : Domestic hot water loading is done automatically at the
comfort set point.
Eco : The temperature maintenance function is deactivated.
DHW set point during release times
Reduced temperature set point outside release times
Unit
Factory set­
ting
%
50
°C
0.5
No
seconds
30
S
Off
°C
25
-
'---'
-
'---'
Factory setting
On
60°C
35°C
7609493 - v11 - 18052020