Potterton SIRIUS THREE FS 70 Installation Manual page 67

Floor-standing condensing gas boiler
Table of Contents

Advertisement

Tab.39
Checking and setting values for gas type G25
Diameter of the Venturi
Diameter of the nozzles
Maximum CO
Tab.40
Authorised CO
2
90
Unit
%
%
%
%
%
%
%
%
%
%
%
(1) The CO
value is valid with the front panel mounted. If the front panel is removed (open chamber), the value readout is lower by 0.2 %.
2
(2) Nominal value.
Tab.41
Authorised CO
2
Unit
%
%
%
%
%
%
%
%
%
%
%
(1) The CO
value is valid with the front panel mounted. If the front panel is removed (open chamber), the value readout is lower by 0.2 %.
2
(2) Nominal value.
Tab.42
Checking and setting values for gas type G31
Diameter of the Venturi
Diameter of the nozzles
Maximum CO
7609493 - v11 - 18052020
Unit
SIRIUS THREE FS
50
mm
24
mm
4.20 (no. 2)
ppm
< 250
ranges for G25 type gas for SIRIUS THREE FS 50 , SIRIUS THREE FS 70 and SIRIUS THREE FS
CO
at maximum power
(1)
2
8.5
8.6
8.7
8.8
8.9
9.0
(2)
9.1
9.2
9.3
9.4
9.5
ranges for G25 type gas for SIRIUS THREE FS 110
CO
at maximum power
(1)
2
8.7
8.8
8.9
9.0
9.1
9.2
(2)
9.3
9.4
9.5
9.6
9.7
Unit
SIRIUS THREE FS
50
mm
24
mm
2.95 (no. 2)
ppm
< 250
SIRIUS THREE FS
SIRIUS THREE FS
70
90
30
34
Variable mixer noz­
6.30 (no. 2)
zles: top part with a
diameter of 5.70
mm, bottom part
with a diameter of
6.50 mm.
< 250
< 250
Authorised CO
7.8 - 8.2
7.9 - 8.3
8.0 - 8.4
8.1 - 8.5
8.2 - 8.6
8.3 - 8.7
8.4 - 8.8
8.5 - 8.9
8.6 - 9.0
8.7 - 9.1
8.8 - 9.2
Authorised CO
8.2 - 8.6
8.3 - 8.7
8.4 - 8.8
8.5 - 8.9
8.6 - 9.0
8.7 - 9.1
8.8 - 9.2
8.9 - 9.3
9.0 - 9.4
9.1 - 9.5
9.2 - 9.6
SIRIUS THREE FS
SIRIUS THREE FS
70
90
30
34
4.0 (no. 2)
4.5 (no. 2)
< 250
< 250
8 Commissioning
SIRIUS THREE FS
110
38
Variable mixer noz­
zles: top part with a
diameter of 6.80
mm, bottom part
with a diameter of
7.70 mm.
< 250
range at minimum power
2
range at minimum power
2
SIRIUS THREE FS
110
38
5.0 (no. 2)
< 250
(1)
(1)
67