Checking Clearances - Siemens SIMATIC IFP1200 Basic Operating Instructions Manual

Hide thumbs Also See for SIMATIC IFP1200 Basic:
Table of Contents

Advertisement

Installing and connecting the device
3.1 Preparing for installation
Dimensions of the mounting cutout
The following table shows the dimensions of the required mounting cutout:
Mounting
cutout
Width w
Height h
*
3.1.5

Checking clearances

The following clearances are required around the device to ensure adequate self-ventilation:
• At least 50 mm to the right and left of the mounting cutout (in x direction) to allow for
insertion of the mounting clips during installation
• At least 50 mm above and below the mounting cutout (in y direction) for ventilation
• At least 10 mm behind the rear panel of the device (in z direction)
The figure below shows the clearances required for horizontal and vertical installation of
SIMATIC IFP Basic device:
24
12 Inch
302
mm
*
+1
208
mm
*
+1
Width and height should be reversed accordingly when mounting in vertical format.
SIMATIC IFP Basic
15 Inch
19 Inch
388.4
mm
455
mm
+1
+1
240.5
mm
279.2
mm
+1
+1
22 Inch
522.2
mm
+1
316.8
mm
+1
Operating Instructions, 06/2023, A5E46178354 - AD
SIMATIC IFP1200
Basic C
12 inch
302
mm
+1
208
mm
+1
IFP Basic