Scheduled Mode; Scheduled + Reheat Mode - Daikin ETVZ16S23DA6V User Reference Manual

Hide thumbs Also See for ETVZ16S23DA6V:
Table of Contents

Advertisement

4
|
Operation

4.7.3 Scheduled mode

4.7.4 Scheduled + reheat mode

User reference guide
38
T t
60°C
50°C
40°C
15°C
00:00
T
DHW tank temperature
t
t
Time
INFORMATION
When the DHW tank mode is reheat, the risk for capacity shortage and comfort
problem is significant. In case of frequent reheat operation, space heating/cooling
function is regularly interrupted.
In scheduled mode the DHW tank produces hot water corresponding to a schedule.
The best time to allow the tank to produce hot water is at night, because the space
heating demand is lower.
Example:
T t
60°C
50°C
40°C
15°C
00:00
T
DHW tank temperature
t
t
Time
Initially, the DHW  tank temperature is the same as the temperature of the
domestic water entering the DHW tank (example: 15°C).
At 00:00 the DHW  tank is programmed to heat up the water to a preset value
(example: Comfort = 60°C).
During the morning, you consume hot water and the DHW  tank temperature
decreases.
At 14:00 the DHW  tank is programmed to heat up the water to a preset value
(example: Eco = 50°C). Hot water is available again.
During the afternoon and evening, you consume hot water again and the
DHW tank temperature decreases again.
At 00:00 the next day, the cycle repeats.
In scheduled + reheat mode, the domestic hot water control is the same as in
scheduled mode. However, when the DHW tank temperature drops below a preset
value (=reheat tank temperature – hysteresis value; example: 35°C), the DHW tank
heats up until it reaches the reheat set point (example: 45°C). This ensures that a
minimum amount of hot water is available at all times.
Example:
1
3
2
4
07:00
14:00
21:00
1
2
4
3
5
07:00
14:00
21:00
t
t
ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P586461-1A – 2020.01