6 Electrical installation
[9.8.1]=3 (Benefit kWh power supply = Safety
thermostat)
1 Open the following (see
"4.2.1 To open the indoor
1 User interface panel
2 Switch box
3 Switch box cover
4 Top cover
2 Connect the safety thermostat (normally closed) cable to the
appropriate terminals as shown in the illustration below.
Note: The jumper wire (factory-mounted) must be removed from the
respective terminals.
3 Fix the cable with cable ties to the cable tie mountings. General
information, see
"6.3.1  To connect the electrical wiring to the
indoor
unit" [ 4  22].
NOTICE
Make sure to select and install the safety thermostat
according to the applicable legislation.
In any case, to prevent unnecessary tripping of the safety
thermostat, we recommend the following:
▪ The safety thermostat is automatically resettable.
▪ The safety thermostat has a maximum temperature
variation rate of 2°C/min.
▪ There is a minimum distance of 2 m between the safety
thermostat and the 3‑way valve.
NOTICE
Error. If you remove the jumper (open circuit) but do NOT
connect the safety thermostat, stop error 8H-03 will occur.
Installation manual
30
INFORMATION
ALWAYS configure the safety thermostat after it is
installed. Without configuration, the unit will ignore the
unit" [ 4  13]):
safety thermostat contact.
4
3
6.3.13

To connect a Smart Grid

2
1
This topic describes 2 possible ways to connect the indoor unit to a
Smart Grid:
▪ In case of low voltage Smart Grid contacts
▪ In case of high voltage Smart Grid contacts. This requires the
installation of the Smart Grid relay kit (EKRELSG).
The 2 incoming Smart Grid contacts can activate the following Smart
Grid modes:
Smart Grid contact
1
0
0
1
1
The use of a Smart Grid pulse meter is not mandatory:
If Smart Grid pulse meter is... Then [9.8.8] Limit setting kW
Used
([9.A.2] Electricity meter 2 ≠
None)
Not used
([9.A.2] Electricity meter 2 =
None)
In case of low voltage Smart Grid contacts
Wires (Smart Grid pulse meter): 0.5 mm²
Wires (low voltage Smart Grid contacts): 0.5 mm²
[9.8.4]=3 (Benefit kWh power supply = Smart grid)
[9.8.5] Smart grid operation mode
[9.8.6] Allow electrical heaters
[9.8.7] Enable room buffering
[9.8.8] Limit setting kW
The wiring of the Smart Grid in case of low voltage contacts is as
follows:
3
4
5
1
2
S
10
S
S11S
S4S
1
/S10S
2
/S11S
1 Connect the wiring as follows:
Smart Grid operation mode
2
0
Free running
1
Forced off
0
Recommended on
1
Forced on
Not applicable
Applicable
X 5M
1
6
7
8
9
10
a
S S
4
a
Jumper (factory-mounted). If you also connect a safety
thermostat (Q4L), replace the jumper with the safety
thermostat wires.
Smart Grid pulse meter
Low voltage Smart Grid contact 1
Low voltage Smart Grid contact 2
Daikin Altherma 3 R MT ECH₂O
is...
ELSH/X(B)12P30+50E
4P708484-1 – 2023.03