6 Electrical installation

a
Drainback connection
b
Spillover connection
c
Hose with non-return valve (1/2")
With installed drainback solar kit (option)
1 Combine the fill and drain kit (option) with the drainback solar
kit (option) to fill the storage tank.
2 Connect the hose with non-return valve to the fill and drain kit.
Follow the steps described in the previous chapter.
5.4.6

To insulate the water piping

The piping in the complete water circuit MUST be insulated to
prevent condensation during cooling operation and reduction of the
heating and cooling capacity.
If the temperature is higher than 30°C and the humidity is higher
than RH 80%, the thickness of the insulation materials should be at
least 20  mm to prevent condensation on the surface of the
insulation.
Installation manual
20
6
Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable
national wiring regulation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical
construction
MUST
legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
CAUTION
Do NOT push or place redundant cable length into the unit.
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50 mm.
6.1

About electrical compliance

Only for the backup heater of the indoor unit
See
"6.3.3 To connect the backup heater power
6.2
Guidelines when connecting the
electrical wiring
Tightening torques
Indoor unit:
Item
M4 (X1M)
M4 (X12M, X15M)
Indoor unit – BUH option:
Item
M4 (X6M) *3V, *6V
M4 (X6M) *9W
6.3

Connections to the indoor unit

Item
Power supply (main)
See
"6.3.2 To connect the main power
supply" [ 4  23].
Power supply (backup
See
"6.3.3 To connect the backup heater
supply" [ 4  24].
heater)
power
Backup heater
See
"6.3.4 To connect the backup heater to
the main
Shut-off valve
See
"6.3.5 To connect the shut-off
valve" [ 4  26].
Electricity meters
See
"6.3.6 To connect the electricity
meters" [ 4  26].
Domestic hot water
See
"6.3.7 To connect the domestic hot
pump" [ 4  27].
pump
water
comply
with
the
applicable
supply" [ 4  24].
Tightening torque (N•m)
1.2
0.88 ±10%
Tightening torque (N•m)
2.45 ±10%
1.2
Description
unit" [ 4  25].
ELSH/X(B)12P30+50E
Daikin Altherma 3 R MT ECH₂O
4P708484-1 – 2023.03