8.2
Description of servicing operations
The combustion performance must be checked before
and after any servicing work on the combustion and
burner components. Refer to section 7.1.
Check "Last fault stored":
B Select Service Function .0 (See page 28 "Selecting
Service Function").
There is a list of the fault codes in the Appendix (see
page 43.
To delete "Last fault stored":
B Turn temperature control
the stop.
B Press and hold the
shows [ ].
The last fault stored has now been deleted.
Checking the ionisation current,
Service Function 3.3
B Select Service Function 3.3 (See page 28 "Select-
ing Service Function").
If the display shows 2 or 3, the ionisation current is OK.
If the display shows 0 or 1, the electrode assembly
(32.1, page 6) must be cleaned or replaced.
Domestic hot water
If the flow rate is too slow:
B remove the domestic hot water heat exchanger and
replace,
B Before removing the heat exchanger shut the inlet
valve and drain the hot water circuit.
B Use new seals when replacing the heat exchanger.
Fig. 49
6 720 611 441 GB (03.11)
anti-clockwise as far as
button until the display
7 181 465 330-06.1R
Primary Heat exchanger
There is a special accessory kit (no. 840) for cleaning
the heat exchanger, order no. 7 719 001 996.
B Check control pressure on the air - gas mixer unit at
max. rated heat output using an electronic manome-
ter.
Fig. 50
The heat exchanger should only be
i
cleaned if the control pressure is
3.0 mbar (R25HE)
5.2 mbar (R30HE)
(depression) or less.
B Remove cleaning access cover (415, page 6) and
the metal plate below it, if present. Refer to fig. 2.
B Unscrew condensation trap and place suitable con-
tainer underneath. Refer to fig. 51.
B Remove the fan and the burner as described in the
text headed "Burner" (see page 36).
Fig. 51
Maintenance
6 720 610 332-69.1R
6 720 610 332-72.1R
35