To Remove The Accessories From The Outdoor Unit; Accessory Pipes: Diameters; To Remove The Transportation Stay - Daikin VRV IV+ RYYQ12U7Y1B Series Installer And User Manual

Hide thumbs Also See for VRV IV+ RYYQ12U7Y1B Series:
Table of Contents

Advertisement

3 About the box
▪ Take care not to damage the unit when removing the shrink foil
with a cutter.
▪ Remove the 4 bolts fixing the unit to its pallet.
WARNING
Tear apart and throw away plastic packaging bags so that
nobody, especially children, can play with them. Possible
risk: suffocation.
8~12 HP
3.3
To remove the accessories from
the outdoor unit
8~12 HP
Make sure that all accessories are available in the unit.
a
b
REQUEST FOR THE INDICATION OF INSTALLATION INFORMATION
1. RECORD OF INDOOR UNIT MODEL AND INSTALLATION SITE
No.
1
2
3
4
MODELNAME
SITE
INSTALLATION
No.
11
12
13
14
MODELNAME
INSTALLATION
SITE
No.
21
22
23
24
MODELNAME
SITE
INSTALLATION
No.
31
32
33
34
MODELNAME
INSTALLATION
SITE
No.
41
42
43
44
MODELNAME
INSTALLATION
No.
SITE
51
52
53
54
MODELNAME
INSTALLATION
No.
SITE
61
62
63
64
MODELNAME
INSTALLATION
SITE
2. RECORD FOR SETTINGS (CONTENTS SEE INSTALLATION MANUAL)
SETTING
VALUE
REMARK
DATE
3. RECORD OF INSTALLATION DATE
DAY
MONTH
YEAR
6. AFTER EQUIPPING, PLEASE PUT IT ON THE BACK SIDE OF THE FRONT PLATE.
f
g
a
General safety precautions
b
Installation manual and operation manual
c
Additional refrigerant charge label
d
Installation information sticker
e
Fluorinated greenhouse gases label
f
Multilingual fluorinated greenhouse gases label
g
Piping accessory bag
Installer and user reference guide
8
14~20 HP
14~20 HP
c
d
e
REQUEST FOR THE INDICATION OF ADDITIONAL REFRIGERANT CHARGING AND LEAK DETECTION OPERATION RESULT
BE SURE TO FILL OUT THE BLANKS, WHICH ARE NEEDED FOR AFTER-SALE SERVICES.
BE SURE TO FILL OUT THE BLANKS, WHICH ARE NEEDED FOR AFTER-SALE SERVICES.
5
6
7
8
9
10
1. CALCULATION OF ADDITIONAL REFRIGERANT CHARGING AMOUNT
CALCULATE THE ADDITIONAL REFRIGERANT CHARGING AMOUNT BASED ON THE FORMULA BELOW BEFORE CHARGING.
SHIPMENT (INDICATED ON THE MACHINE NAMEPLATE) AND THE ADDITIONAL AMOUNT SHOWN AS FOLLOWS :
WHEN RE-CHARGING TOTAL AMOUNT OF REFRIGERANT , CHARGE THE TOTAL OF THE AMOUNT CHARGED AT
Total indoor unit
15
16
17
18
19
20
kg
capacity connection
Total indoor unit capacity
50%< CR < 105%
ratio (CR)
8HP
10-12HP 14-16HP 18-20HP
0
0
0
0.5
OUTDOOR
ADDITIONAL CHARGING
AMOUNT
PIPE SIZE O22.2 x 0.37
TOTAL LENGTH OF LIQUID
PIPE SIZE O19.1 x 0.26
TOTAL LENGTH OF LIQUID
TOTAL LENGTH OF LIQUID
PIPE SIZE O15.9 x 0.18
when piping length <30m
50%< CR < 70%
105%< CR < 130%
0.5
0
0
0.5
0.5
0
0.5
1.0
25
26
27
28
29
30
UNIT
kg
(m) x 0.37
(m) x 0.26
(m) x 0.18
when piping length >30m
Total indoor unit capacity
70%< CR < 85%
85%< CR < 105%
0.7
0.3
0.5
1
0.5
1
1.5
1.0
105%< CR < 130%
1.2
1.5
1.5
2.0
PIPE SIZE O12.7 x 0.12
TOTAL LENGTH OF LIQUID
PIPE SIZE O9.5 x 0.059
TOTAL LENGTH OF LIQUID
PIPE SIZE O6.4 x 0.022
TOTAL LENGTH OF LIQUID
35
36
37
38
39
40
(m) x 0.12
(m) x 0.059
(m) x 0.022
kg
ONLY FOR RYYQ8~20 MODELS
RYYQ8~12
RYYQ14-16
RYYQ18-20
0.9
1.1
1.3
2. RECORD OF ADDITIONAL REFRIGERANT CHARGE AMOUNT AND RESULT OF LEAK CHECK OPERATION
45
46
47
48
49
50
DATE
AMOUNT
55
56
57
58
59
60
RESULT LEAK CHECK
DATE
AMOUNT
RESULT LEAK CHECK
DATE
AMOUNT
SETTING
VALUE
REMARK
DATE
RESULT LEAK CHECK
DATE
AMOUNT
RESULT LEAK CHECK
3. FOR DETAILS CONCERNING PIPING SELECTION AND CALCULATION OR HOW TO OPERATE THE LEAK DETECTION FUNCTION, PLEASE REFER TO THE INSTALLATION MANUAL.
4. MODEL NAME
5. MANUFACTURING NUMBER
4. AFTER FILLING IN THIS TABLE, PLEASE PUT IT ON THE SWITCH BOX COVER.
3P328191-1
3P328192-1
3.4

Accessory pipes: Diameters

Accessory pipes (mm)
Gas pipe
▪ Front connection
ID Øa
ID Øb
▪ Bottom connection
ID Øa
OD Øb
Liquid pipe
▪ Front connection
ID Øb
ID Øa
▪ Bottom connection
ID Øb
ID Øa
(a)
Equaliser pipe
▪ Front connection
ID Øa
ID Øb
▪ Bottom connection
ID Øa
OD Øb
(a)
Only for RYMQ models.
3.5

To remove the transportation stay

Only for 14~20 HP
NOTICE
If the unit is operated with the transportation stay attached,
abnormal vibration or noise may be generated.
The transportation stay installed over the compressor leg for
protecting the unit during transport must be removed. Proceed as
shown in the figure and procedure below.
1 Slightly loosen the fixing nut (a).
2 Remove the transportation stay (b) as shown in the figure
below.
3 Tighten the fixing nut (a) again.
2
2
HP
Øa
Øb
8
25.4
19.1
10
22.2
12
28.6
14
16
18
20
8
9.5
10
12
9.5
12.7
14
12.7
16
18
12.7
15.9
20
8
19.1
10
12
19.1
22.2
14
16
18
25.4
28.6
20
3 (12.3 N·m)
3 (12.3 N·m)
1
1
a
b
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1 – 2018.09

Advertisement

Table of Contents
loading

Table of Contents