Wiring Diagram: Outdoor Unit - Daikin VRV IV+ RYYQ12U7Y1B Series Installer And User Manual

Hide thumbs Also See for VRV IV+ RYYQ12U7Y1B Series:
Table of Contents

Advertisement

12 Technical data
12.4

Wiring diagram: Outdoor unit

Refer to the wiring diagram sticker on the unit. The abbreviations
used are listed below:
INFORMATION
The wiring diagram on the outdoor unit is only for the
outdoor unit. For the indoor unit or optional electrical
components, refer to the wiring diagram of the indoor unit.
1
This wiring diagram applies only to the outdoor unit.
2
Symbols (see below).
3
When using the optional adapter, refer to the installation
manual of the optional adapter
4
For connection wiring to indoor–outdoor transmission F1‑F2,
outdoor‑outdoor transmission F1‑F2, outdoor‑multi
transmission Q1‑Q2, refer to the installation manual.
5
How to use BS1~BS3 switch, refer to the "Service
Precaution" label on the electrical component box cover.
6
When operating, do NOT short-circuit the protection devices
(S1PH).
7
Only for RYYQ model
8
Only for RYYQ/RYMQ model
9
For 8~12 HP: Connector X1A (M1F) is white, connector X2A
(M2F) is red.
9
For 14~20 HP: Colours (see below).
10 Colours (see below).
Legend for wiring diagram 8~12 HP:
A1P
Printed circuit board (main)
A2P
Printed circuit board (noise filter)
A3P
Printed circuit board (inverter)
A4P
Printed circuit board (fan)
A5P
Printed circuit board (ABC I/P) (option)
BS1~BS3
Push button switch (MODE, SET, RETURN)
(A1P)
C* (A3P)
Capacitor
DS1, DS2
DIP switch
(A1P)
E1HC
Crankcase heater
E3H
Drain pan heater (option)
F1U, F2U
Fuse (T 31.5 A / 250 V)
(A1P)
F3U
Field fuse
F101U
Fuse
(A4P)
F401U,
Fuse
F403U
(A2P)
F601U,
Fuse
(A3P)
HAP (A*P)
Pilot lamp (service monitor is green)
K3R (A3P)
Magnetic relay
K4R (A1P)
Magnetic relay (Y1S)
K5R (A1P)
Magnetic relay (Y2S)
K6R (A1P)
Magnetic relay (E3H)
K7R (A1P)
Magnetic relay (E1HC)
K9R (A1P)
Magnetic relay (Y3S)
K11R (A1P) Magnetic relay (Y5S)
L1R
Reactor
Installer and user reference guide
58
M1C
Motor (compressor)
M1F
Motor (fan)
PS (A1P,
Switching power supply
A3P)
Q1DI
Earth leakage circuit breaker (field supply)
Q1LD (A1P) Earth current detector (field supply)
R24 (A4P)
Resistor (current sensor)
R300 (A3P) Resistor (current sensor)
R1T
Thermistor (air)
R3T
Thermistor (accumulator)
R4T
Thermistor (heat exchanger, liquid pipe)
R5T
Thermistor (subcool liquid pipe)
R6T
Thermistor (heat exchanger, gas pipe)
R7T
Thermistor (heat exchanger, de-icer)
R8T
Thermistor (M1C body)
R21T
Thermistor (M1C discharge)
S1NPH
Pressure sensor (high)
S1NPL
Pressure sensor (low)
S1PH
Pressure switch (discharge)
SEG1~SEG
7-segment display
3 (A1P)
T1A
Current sensor
V1D (A3P)
Diode
V1R (A3P,
Power module
A4P)
X*A
Connector
X1M (A1P)
Terminal block (control)
X1M (A5P)
Terminal block (power supply)(option)
Y1E
Electronic expansion valve (main)
Y2E
Electronic expansion valve (injection)
Y3E
Electronic expansion valve (liquid cooling)
Y4E
Electronic expansion valve (storage vessel)
Y1S
Solenoid valve (main)
Y2S
Solenoid valve (accumulator oil return)
Y3S
Solenoid valve (oil 1)
Y5S
Solenoid valve (subcool)
Z*C
Noise filter (ferrite core)
Z*F (A2P,
Noise filter (with surge absorber)
A5P)
Connectors for optional accessories:
X10A
Connector (drainpan heater)
X37A
Connector (power adapter)
X66A
Connector (remote switching COOL/HEAT selector)
Legend for wiring diagram 14~20 HP:
A1P
Printed circuit board (main)
A2P, A5P
Printed circuit board (noise filter)
A3P, A6P
Printed circuit board (inverter)
A4P, A7P
Printed circuit board (fan)
A8P
Printed circuit board (ABC I/P) (option)
BS1~BS3
Push button switch (MODE, SET, RETURN)
(A1P)
C* (A3P,
Capacitor
A6P)
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1 – 2018.09

Advertisement

Table of Contents
loading

Table of Contents