Chapter 6
Certification
Test
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 61000-4-29
IEC 60255-5
34
Description
Surge
Induced (Conducted) RFI
Magnetic Field
Voltage Dips and Interrupts
Damped Oscillatory
Mains Frequency Voltage
Ripple on DC Power Supply
Voltage Dips and Interrupts
Dielectric Strength
HV Impulse
AC Power Ports
Earth
Ground Ports
Signal Ports
± 4 kV Line-to-Ground
DC Power Ports
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
AC Power Ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
Signal Ports
DC Power Ports
AC Power Ports
Earth
Ground Ports
Enclosure Ports
40 A/m Continuous
AC Power Ports
100% for 5 Periods
100% for 50 Periods
Signal Ports
2.5 kV Common Mode @ 1 MHz
1 kV Differential Mode @ 1 MHz
DC Power Ports
2.5 kV Common Mode @ 1 MHz
1 kV Differential Mode @ 1 MHz
AC Power Ports
2.5 kV Common Mode @ 1 MHz
1 kV Differential Mode @ 1 MHz
Signal Ports
DC Power Ports
DC Power Ports
DC Power Ports
Signal Ports
2 kV (Failsafe Relay Output)
DC Power Ports
AC Power Ports
Signal Ports
5 kV (Failsafe Relay Output)
DC Power Ports
AC Power Ports
Installation Guide
Test Levels
± 4 kV
± 4 kV
± 2 kV
10 V
10 V
10 V
10 V
1000 A/m for 1 s
30 V Continuous
300 V for 1 s
30 V Continuous
300 V for 1 s
10%
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
1.5 kV
2 kV
5 kV
5 kV
EMC and Environmental Type Tests
RUGGEDCOM RS900
Severity Levels
4
4
4
3
4
3
3
3
3
3
3
3
4
4
3