Toshiba BMS-SM1280ETLE Service Manual page 47

Smart manager with data analyzer
Table of Contents

Advertisement

13-4-7. Communication error with the digital input / output relay
interface is displayed.
No.
1
The digital input / output relay interface is not turned on. Check if the "POWER" LED of the digital input / output relay interface
2
The RS-485 communication wiring is not connected or
disconnected.
3
The RS-485 communication wiring is incorrect or
connected with wrong polarity.
4
The terminal resistance is not connected.
5
The wiring length is too long.
6
The communication circuit of the digital input / output
relay interface failed.
7
The communication circuit of the controller failed.
8
Noise is superposed on the communication wiring.
9
The communication cable in use is not the specified
one. (Wire diameter is smaller)
The address switch setting of the digital input / output relay interface does not match that in the setting file.
No.
3
The RS-485 wiring is defective between the digital input
/ output relay interface and the controller.
13-4-8. Communication error with the energy monitoring relay
interface is displayed.
No.
1
The energy monitoring relay interface is not turned on. Check if the "POWER" LED of the energy monitoring relay interface
2
The address switch setting of the energy monitoring
relay interface does not match that in the setting file.
13-4-9. Page breaks in alarm email were deleted, everything
appears in one line.
No.
1
Specifications for Outlook (deleting excess page
breaks).
Cause
Cause
Cause
Cause
illuminates.
Check the conduction of the communication wiring.
Check the terminal block connected.
Check the value of the terminal resistance with a tester.
Change it to the specified wiring length.
Replace with the normal digital input / output relay interface and check that
the communication is available.
Replace with the normal controller and check that the communication is
available.
Check the waveform between RS-485 communication wiring A and B.
If noise is superposed, identify the noise source and remove it.
Change it to the specified communication cable.
1.Check the address switch setting of the digital input / output relay
interface and the setting in the setting file.
2.Check if the RS-485 LED (Green) of the digital input / output relay
interface blinks.
illuminates.
1.Check the address switch setting of the energy monitoring relay
interface and the setting in the setting file.
2.Check if the RS-485 LED (Green) of the energy monitoring relay
interface blinks.
1.While the email is open in Outlook, select the [Format] menu, and
deselect the [Unwrap Text] check box.
2.Use an email software other than Outlook.
47
Solution
Solution
Solution
Solution

Advertisement

Table of Contents
loading

Table of Contents