Toshiba BMS-SM1280ETLE Service Manual page 21

Smart manager with data analyzer
Table of Contents

Advertisement

<DS23>
<1> Smart Manager with data analyzer main / sub selection
OFF: Main
ON: Sub
Normally, this bit is set to OFF.
When two Smart Manager with data analyzer units are used as a main
unit and a sub unit with the same mode setting, set this bit to OFF
(Main) for one unit and to ON (Sub) for the other unit.
<2> to <5> Control group selection
Control group selection
All groups
Group 1 ~ 16
Group 17 ~ 32
Group 33 ~ 48
Group 49 ~ 64
These bits specify a group range used in the control group selection.
The Smart Manager with data analyzer for which control group selection
is set controls only groups within the set group range.
To use the control group selection, set DS23-<2> to <5> and DS24-<5>
to <6>. For details, see "9. Mode setting for Smart Manager with data
analyzer".
<6> Central control / remote controller mode selection
OFF: Central control mode
ON: Remote controller mode
Central control mode:
Remote controller mode: The Smart Manager with data analyzer is
<7> Central control Main / Sub selection
OFF: Main
ON: Sub
This setting is required when multiple Smart Manager with data analyzer
units are used or another central control unit is used.
(1) Set this bit to OFF when one Smart Manager with data analyzer unit
is used.
(2) When multiple central control units are used as a main unit and sub
units, set to OFF (Main) for one unit and set to ON (Sub) for other
units.
DS24-<6>
OFF
ON
ON
ON
ON
The Smart Manager with data analyzer is
used as the central control device.
used as the remote controller.
DS23
-
<2> ON
<3> ON
<4> ON
<5> ON
21
Factory default: All OFF
DS23
1
2 3 4 5 6 7 8
ON
OFF
<8> Central button enable /
disable
OFF:
button operation is
permitted
ON:
button operation is
inhibited
* The
button is disabled in
the remote controller mode
regardless of this setting.