(10) Base heater ON/OFF output control (Option)

(i)
Base heater ON conditions
When all of following conditions are met, the base heater is turned ON.
・ Outdoor air temperature (detected with Tho-A) is 3°C or lower.
・ In the heating mode
・ When the compressor is turned ON
(ii) Base heater OFF conditions
When either one of following conditions is met, the base heater is turned OFF.
・ Outdoor air temperature (detected with Tho-A) is 5°C or higher.
・ When the compressor stop has been detected for 30 minutes continuously
・ In the cooling or dehumidifying mode
Base heater ON
Base heater OFF
3
5
Outdoor air temperature (°C) [Tho-A]
83
-
-
'17 • PAC-T-257