Technical data
6.2 Output
Product feature/connecting
outputs in parallel
Switching on outputs
Shutdown characteristics SITOP select:
Figure 6-1
● An output current is continuously permissible up to the selected current response
threshold.
● In the range 101...129 % of the selected current response threshold, an overload current
is permissible for 5 seconds; after this time, the output is electronically shut down.
● In the range > 130 % of the selected current response threshold, the current is limited to
130 %; after approximately 50 ... 100 ms the output is electronically shut down.
● When the output current exceeds the selected current response threshold, and if the
supply voltage simultaneously dips below 20 V, then the output is electronically
shutdown.
46
6EP1961-2BA00
No
All outputs are simultaneous-
ly switch on after the supply
voltage has ramped up,
delay time of 24 ms or
100 ms can be programmed
for outputs to be sequentially
switched on.
Shutdown characteristic SITOP select
6EP1961-2BA11
6EP1961-2BA31
No
All outputs are simultaneously switched-on after the supply
voltage ramps up > 20 V, delay time of 25 ms, 100 ms – or
"load optimized" where the outputs are sequentially
switched-on, selected using the DIP switch.
Manual, 12.2014, C98130-A7579-A1-1-7629
6EP1961-2BA21
6EP1961-2BA41
No