Description, device design, dimension drawing
2.6 Electronic overload shutdown and reset
● In the range > 150 % of the selected current response threshold, the current is limited to
150 %, at the earliest after 100 ms the output is electronically shut down (LED of the
output is lit red).
● When the output current exceeds the selected current response threshold, and if the
supply voltage simultaneously dips below 20 V, then the output is electronically shutdown
(the LED of the output is lit red).
Reset of an electronic overload shutdown using the reset button and remote reset
Figure 2-12
An individual output can be reset using the button. This resets the electronic shutdown of the
output, caused by an overload condition.
The initial situation is an electronic shutdown of individual outputs as a result of an overload
condition. This is signaled using the LED
LED
Lit red
Flashes red
Lit green
Procedure to reset an electronic shutdown:
1. After an electronic shutdown (LED of the output is lit red), allow a wait time of 20 seconds
to elapse.
2. Press the reset button
Electronic shutdown was reset, and the output has been switched-on again (LED of the
output is lit green).
22
SITOP PSE200U button
Meaning/handling
Electronic shutdown as a result of an overload; wait time until a reset is possible:
approx. 20 seconds.
Output ready for a reset; press the button to switch-on the output again.
The reset was carried out, the output was switched-on again.
of the particular output
of the particular output.
Manual, 12.2014, C98130-A7579-A1-1-7629
Selectivity modules