Meaning of STOP-ACTIVE LED
The following table shows the meaning of the STOP-ACTIVE LED of the CPU 1515‑2 PN.
Table 5-3  Meaning of the LED
STOP-ACTIVE LED
LED lit yellow
LED off
CPU 1515-2 PN (6ES7515-2AN03-0AB0)
Equipment Manual, 11/2022, A5E46416198-AC
The CPU has been switched to STOP mode using the STOP button.
As long as the STOP-ACTIVE LED is lit up, switching the CPU to RUN mode is only possible
using the RUN button.
The CPU can then no longer be set to RUN mode via display operation or via online functions.
The state of the buttons is retained at power-off. If the CPU does not start up automatically
after a power-on, you have to keep the STOP button pressed during startup until the STOP-
ACTIVE LED is activated.
If an automatic startup is to be reliably prevented after a power-on, the STOP button has to
be kept pressed during the startup of the CPU until the STOP-ACTIVE LED is activated.
The CPU has been set to STOP mode using the display or programming device/PC and not
with the STOP button on the device.
The CPU is in RUN mode.
Interrupts, error messages, diagnostics and system alarms
5.1 Status and error display of the CPU
Meaning