The Select module screen is displayed.
3.
Select the UPM you want to shut down.
4.
In the UPM control screen, select Shut down module.
7.6
A UPS emergency power-off is initiated by the EPO pushbutton switch. In case
of an emergency, you can use this switch to control the UPS output. The EPO
switch de-energizes the critical load and powers down the UPS immediately
without asking for verification. The UPS, including the static bypass switch,
remains off until it is restarted.
When the EPO switch is activated, all power to the critical load is lost. Use
this feature only in case of emergency.
Note: The following instructions are for the EPO switch supplied by Eaton
Corporation. If you are using a customer-supplied EPO switch, it may not
activate in the same way. For operating instructions, see the documentation
provided with the switch.
To use the EPO switch:
1.
Press the EPO pushbutton switch.
The input, output, and bypass backfeed relays open, the battery breaker or
disconnect is tripped, and the power module is turned off immediately,
without asking for verification.
To restart the UPS after using the EPO pushbutton, reset the EPO switch and
then follow the procedure in Section
Do not attempt to restart the system after using the EPO switch until the
conditions for safe start-up have been confirmed.
7.7
the maintenance bypass mode
Only trained personnel who are familiar with the behavior and functions of the
UPS are allowed to operate the internal MBS. A full UPS wiring diagram with
MBS switch is presented in the schematic diagram.
Note: The internal MBS and static bypass must be supplied by the same
source.
©
Eaton Corporation plc 2018. All rights reserved.

Using the Remote Emergency Power-off switch

Turning the UPS from the double conversion mode to
CAUTION
7.3.1
or Section
WARNING
Revision: 005
Document ID: P-164000493
User's and installation guide
7.3.2
.
96 (117)

Advertisement

Table of Contents
loading

This manual is also suitable for:

93ps ups 8-40 kw

Table of Contents