1.
Select the CONTROLS symbol in the main menu bar.
The System Control screen is displayed.
2.
Select Battery in the System Control screen.
3.
In the Battery System Control screen, select the RESTING → TESTING
command and press the
7.3.12
A UPS Load Off is initiated by selecting the Load Off command in the UPS
Control screen. The UPS LOAD OFF controls the UPSs output by powering
down the UPS and de-energizing the critical load.
The UPSs (including bypass) remains off until restarted.
To use the LOAD OFF command:
1.
Select the CONTROLS symbol in the main menu bar on the UPS to be
shut down.
The System Control screen is displayed.
2.
Select UPS in the System Control screen.
3.
In the UPS System Control screen, select the NORMAL → LOAD OFF or
BYPASS → LOAD OFF command depending on the UPS mode, then press
the
The Verify Action screen is displayed, providing you with a choice to
proceed or abort the shutdown.
All power to the critical load is lost when the LOAD OFF command is
confirmed in the following step. You should use this feature only when
you want to de-energize the critical load.
4.
Select Yes or No and press the
Selecting Yes immediately shuts down the UPS and de-energizes the
critical load. Selecting No aborts the shutdown.
5.
To restart the UPS after pressing the LOAD OFF push button, follow the
procedure in Sections
Power is present inside the UPS cabinet after the upstream input feeder
circuit breakers are opened because of the installed external battery
cabinet.
7.3.13
A UPS emergency power-off is initiated by the remote EPO push-button switch.
In case of an emergency, you can use this switch to control the UPS output. The
©
Eaton Corporation plc 2019. All rights reserved.

Using the UPS LOAD OFF command

push button.
7.3.1

Using the remote emergency power-off switch

push button.
CAUTION
push button.
7.3.2
or
.
WARNING
Revision: 002
Document ID: P-164000848
User's and installation guide
94 (118)

Advertisement

Table of Contents
loading

This manual is also suitable for:

93e g2 120/12093e g2 200/16093e g2 200/200

Table of Contents