Bryant 569J 08G Series Installation, Start-Up And Service Instructions Manual page 11

Air-cooled condensing units, 60 hz, single circuit, 2-stage with digital scroll compressor and puronr (r-410a) refrigerant-size 08
Table of Contents

Advertisement

Field Power Supply —
If equipped with optional Powered Convenience Outlet:
The power source leads to the convenience outlet's
transformer primary are not factory connected. Installer
must connect these leads according to required operation
of the convenience outlet. If an always-energized
convenience outlet operation is desired, connect the
source leads to the line side of the unit-mounted
disconnect. (Check with local codes to ensure this method
is acceptable in your area.) If a de-energize via unit
disconnect switch operation of the convenience outlet is
desired, connect the source leads to the load side of the
unit disconnect. On a unit without a unit-mounted
disconnect, connect the source leads to compressor
contactor C and indoor fan contactor IFC pressure lugs
with unit field power leads..
Refer to Fig. 13 for power transformer connections and the
discussion on connecting the convenience outlet on page 12.
Field power wires are connected to the unit at line-side
pressure lugs on compressor contactor C and TB1 (see
wiring
diagram
label
for
arrangement) or at factory-installed option non-fused
disconnect switch. Max wire size is #4 AWG (copper only).
NOTE: TEST LEADS - Unit may be equipped with short
leads (pigtails) on the field line connection points on
contactor C or optional disconnect switch. These leads are
for factory run-test purposes only; remove and discard
before connecting field power wires to unit connection
points. Make field power connections directly to line
connection pressure lugs only.
WARNING
!
FIRE HAZARD
Failure to follow this warning could cause in personal
injury, death and/or equipment damage.
Do not connect aluminum wire between disconnect
switch and condensing unit. Use only copper wire.
(See Fig. 8.)
ELECTRIC
DISCONNECT
SWITCH
WIRE ONLY
ALUMINUM
Fig. 8 - - Disconnect Switch and Unit
Units with Factory-Installed Non- - Fused Disconnect —
The factory- - installed option non- - fused disconnect (NFD)
switch is located in a weatherproof enclosure located
under the main control box. The manual switch handle and
shaft are shipped in the disconnect enclosure. Assemble the
control
box
component
COPPER
WIRE
A93033
shaft and handle to the switch at this point. Discard the
factory test leads (see Fig. 9).
Units Without Disconnect Option
C
11
Disconnect
L1
208/230-3-60
Units With Disconnect Option
L1
2
Optional
Disconnect
L2
4
L3
6
Disconnect factory test leads; discard.
Fig. 9 - - Power Wiring Connections
Connect field power supply conductors to LINE side
terminals when the switch enclosure cover is removed to
attach the handle.
Fig. 10 - - Location of Non- - Fused Disconnect Enclosure
To field install the NFD shaft and handle:
1. Remove the unit front pane (see Fig. 2).
2. Remove (3) hex screws on the NFD enclosure - - (2) on
the face of the cover and (1) on the left side cover.
3. Remove the front cover of the NFD enclosure.
4. Make sure the NFD shipped from the factory is at
OFF position (the arrow on the black handle knob is
at OFF).
5. Insert the shaft with the cross pin on the top of the shaft
in the horizontal position.
11
TB1
13
per
NEC
L2
L3
460-3-60
575-3-60
1
Factory
3
Wiring
Switch
5
C10204
C12284

Advertisement

Table of Contents
loading

This manual is also suitable for:

569j 08h series

Table of Contents