Bryant 569J 08G Series Installation, Start-Up And Service Instructions Manual page 18

Air-cooled condensing units, 60 hz, single circuit, 2-stage with digital scroll compressor and puronr (r-410a) refrigerant-size 08
Table of Contents

Advertisement

Using plotted operating point:
If plotted operating condition is - -
BELOW the curve
ABOVE the curve
150
130
110
90
70
50
30
140
Adjust charge by - -
REDUCE charge
ADD charge
7.5 TON DUAL STAGE CHARGING CHART PURON
(COMPRESSOR FULL LOAD, ALL CONDENSER FANS OPERATING)
DIAGRAMME DE REMPLISSAGE DE PURON POUR 7.5 TONNES, 2 STAGE
(COMPRESSEUR À PLEINE CAPACITÉ, TOUS LES VENTILATEURS DU
CONDENSEUR EN OPÉRATION)
190
240
290
PRESSURE AT LIQUID VALVE (PSIG)
PRESSION À LA VANNE DE LIQUIDE (PSIG)
Fig. 19 - - 569J*08G/H Charging Chart
Final Checks —
Ensure that all safety controls are operating, control panel
covers are on, and the service panels are in place.
340
390
440
490
38AU000028 Rev -
18
540
590
C14293