■ Never operate a system that is improperly
adjusted or has faulty interlocks or limit
switches. Always replace faulty equipment with
new equipment before resuming operation.
Operating a system
equipment can cause explosions, injuries, and
property damage.

Maintenance

■ High voltage, turn off power before
disconnecting or installing sensors or controls.
All burner systems must be maintained to ensure their
safe operation. The operator of this equipment must be
trained in safe operating procedures. The owner and
operator must set a regularly scheduled maintenance
interval based on recommendations from the equipment
manufacturers, environmental conditions, and their own
operational history.

System Checks

Periodically test the sensors as described in the Test
Procedure section.
Sensor Lens
Clean the glass lens regularly with a soft, damp cloth.
The presence of foreign material will measurably
reduce the flame signal strength.
Rotation
To ensure operability of stored items and to reduce the
possibility of extended down-time, periodically swap
spare sensors and control units with active ones.
6
WARNING
with defective safety
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวี ว ั ฒ นา กทม. 10170.
website:
https://www.add-furnace.com/
Line ID: @add11 e-mail: add028883472@gmail.com
Eclipse 90° UV Scanner, V2, Instruction Manual 852, 5/26/2016