Appendix - Siemens GMSG Instruction Manual

Vacuum circuit breaker
Hide thumbs Also See for GMSG:

Advertisement

Appendix

Table 9: Circuit breaker control data
Control voltages,
ANSI/IEEE C37.06
Nominal
Range
Close
24 Vdc
19 - 28
14 - 28
48 Vdc
36 - 56
28 - 56
125 Vdc
100 - 140
70 - 140
250 Vdc
200 - 280
140 - 280
120 Vac
104 - 127
240 Vac
208 - 254
Table 10: Interrupting capacity auxiliary switch contacts
Type switch
Continuous
current
Non-inductive
A
Circuit breaker
10
TOC
15
MOC
20
Inductive
Circuit breaker
10
TOC
15
MOC
20
62
Close
Trip
coil
coil
Trip
A
A
1
1
5.7
15/----
4
11.4
11.4/30
3
2.1
4.8/7.4
3
2.1
4.2/9.6
3
----
2.0
----
4
2, 4
----
4
2.0
----
2,4
2
Control circuit voltage
120 Vac 240 Vac
10
5
15
10
15
10
6
3
15
10
15
10
Spring charging motor
Run
Inrush
Charging
(Average)
(Peak)
1
A
A
Seconds
----
4
----
4
----
8
25
10
4
18
10
2
10
10
6
----
10
4
3
----
4
10
48 Vdc 125 Vdc 250 Vdc
10/30
9.6
1
0.5
0.5
10
10
10
6
0.5
0.5
10
10
Footnotes:
Current at nominal voltage
1.
Capacitor trip
2.
3.
Value preceding slash (/) is the
current for the standard trip coil
with standard rating interrupting
time. Value following (/) is current
for optional trip coil with three-
4
cycle interrupting time.
4.
---- means this selection is not
available.
Footnotes:
Two contacts in series
1.
All switch contacts are non-
2.
convertible.
4.8
0.2
5
3
0.2
5