Appendix

Table 7: Technical ratings
Rated withstand
voltages
Rated
Lightning
maximum
impulse
voltage
(BIL)
Circuit
breaker
type
kV, rms
kV
3
38.0-25
38.0
200/258
38.0-31.5
38.0
200/258
38.0-40
38.0
200/258
Addtional key ratings for SDV-R and
SDV-R-AR:
Rated closing time <45 ms
Rated opening time <30 ms
Rated mechanical switching time
(vacuum circuit breaker open to ground
switch close) 12-16 ms
Grounding switch rated short-time
current 12.5 kA
Grounding switch rated closing and
latching current 32.5 kA.
Table 8: Control data
Stored-energy operator
Range
Nominal
Close
Trip
125 Vdc
90-140
70-140
250 Vdc
180-280
140-280
120 Vac
104-127
104-127
240 Vac
208-254
208-254
Instruction manual
Rated
short-
circuit and
Rated
Power
short-time
interrupting
frequency
current
time
1
kV
kA, rms
ms/cycles
80
25
50/3
80
31.5
50/3
80
40
50/3
Addtional key ratings for SDV-R-AR:
Rated accessibility type 2B
Rated internal arcing short-circuit
current 25, 31.5, or 40 kA
Rated arcing duration 0.5 s.
Close coil
Trip coil
1, 6
A
A
2.1
7.4/4.8
2.1
9.6/4.2
2.0
2.0
| Types SDV-R and SDV-R-AR distribution circuit breakers
Rated transient
recovery voltage
Rated
u
TRV
t
time to
c
3
continuous
peak
voltage
current
value
u
c
A, rms
kV
μs
1,200,
71.7
59
2,000
1,200,
71.7
59
2,000
1,200,
71.7
59
2,000
Footnotes:
1.
2.
Footnotes:
1.
Spring charging motor
Amperes
Charging
2.
run (avg.)
seconds
4
10
2
10
6
10
3
10
Rated
Rated
2
permissible
closing
tripping
and
delay time
latching
Y
current
sec
kA, peak
2
65
2
82
2
104
TRV values are in accordance
with ANSI/IEEE C37.04-2018
First value is full-wave impulse
withstand circuit breaker open
or closed. Second value is
chopped-wave impulse
withstand, applicable only
with circuit breaker closed.
First value is for standard 50 ms/
three-cycle interrupting time.
Second value is for optional 83
ms/five-cycle interrupting time
For stored-energy operator,
power requirement for second
trip coil is approximately 70 W
(dc) or 50 VA (ac). Power
requirement for undervoltage
device is approximately 20 W
(dc) or 20 VA (ac).
53