Recommended Exhaust Pipe Transitions; Two (2) Pipe Common Direct Vent Systems - Westinghouse Premium WGRT 199 Series Installation, Start-Up, Maintenance, Parts, Warranty

Residential tankless water heaters
Hide thumbs Also See for Premium WGRT 199 Series:
Table of Contents

Advertisement

36

2. Recommended Exhaust Pipe Transitions

Figure 29 - Recommended Exhaust Pipe Transitions

3. Two (2) Pipe Common Direct Vent Systems

DO NOT ATTEMPT to common vent 150 model water heaters!
Doing so will result in property damage, severe personal injury,
or death.
Common Vented units must be direct vented, with an exhaust vent
and intake air pipe vented to the outdoors. DO NOT power vent
Common Vented units! Doing so will result in property damage,
severe personal injury, or death.
The unit can be direct vented without any modification using a 3
inch diameter pipe. The following diagrams represent some typical
direct venting configurations and are included to assist in designing
whl-004 Rev. 000 Rel. 013 Date 5.1.18
the vent system. Possible configurations are not limited to the
following diagrams. See Table 20 for trunk line sizing when common
venting multiple heaters.
For each floor containing bedroom(s), a carbon monoxide detector
and alarm shall be placed in the living area outside the bedrooms,
as well as in the room that houses the heater. Detectors and alarms
shall comply with NFPA 720 (latest edition). Failure to comply with
these requirements could result in product damage, severe personal
injury, or death.