Heating Circuit 1 And 2 Functions - Fujitsu WSYA050ML3 Design & Technical Manual

Table of Contents

Advertisement

3-4. Heating circuit 1 and 2 functions

• Heating circuit 1
Line
Access
710
U
712
U
714
U
716
S
720
I
721
I
I
730
When the average of the outdoor temperatures over the past 24 hours reaches 18°C, the
regulator switches off the heating (as an economy measure). During summer mode, the display
shows "Eco". This function is only active in automatic mode.
I
740
(With dynamic radiator, adjust from 30 to 35°C)
I
Floor heating system = 50°C/Radiator = 65°C
741
Important
Maximum temperature limitation is not a safety function as required by ground heating.
750
S
S
As soon as the room temperature = [Setpoint line 710 (ex. 20°C) + Room temperature limitation
setpoint line 760 (ex. 0.5°C)] > 20.5°C → The heat pump is stopped.
760
It restarts when the room temperature falls below the setpoint.
(ex. room temperature < 20.0°C)
780
S
790
S
791
S
800
S
801
S
830
S
834
S
3-4. Heating circuit 1 and 2 functions
Function
Comfort setpoint
Reduced setpoint
Frost protection setpoint
Comfort setpoint maximum
Heating curve slope
Offset of the heating curve
Summer/winter heating
limitations
Flow temperature setpoint
minimum
Flow temperature setpoint
maximum
Room influence
Room temperature limitation 0.5...4°C
Quick setback
Optimum start control
maximum
(Early start to switch to the
comfort setting)
Optimum stop control
maximum
(Early stop to switch from the
comfort setting to the
reduced setting)
Reduced setpoint increase
start
Reduced setpoint increase
end
Mixer valve boost
Actuator running time
Setting range or display
Reduced setpoint...Comfort
setpoint maximum
Frost protection
setpoint...Comfort setpoint
4 °C...Reduced setpoint
20...35°C
0.1... 4
-4.5...4.5°C
8...30°C
8°C...Flow temp setpoint
maximum
Flow temp setpoint
minimum...70°C
1...100%
Off
Down to reduced setpoint
Down to frost protection
setpoint
0...360 minutes
0...360 minutes
-30...10°C
-30...10°C
0...50°C
30...873 seconds
- (03-12) -
Setting
Factory
increment
setting
0.5°C
20°C
0.5°C
19°C
0.5°C
8°C
1°C
28°C
0.02
0.5
0.5°C
0°C
0.5°C
18°C
1°C
17°C
1°C
60°C
1%
50%
0.5°C
0.5°C
Off
10 minutes
180 minutes
10 minutes
30 minutes
1°C
---°C
1°C
-5°C
1°C
0°C
1 second
240 seconds
3. Function table

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents