Capacity Request (System Lv); Damper Position; Excess Air Management - Trane TZON1050 Installation Manual

Communicating connected control
Table of Contents

Advertisement

Installation Guide
Example for determining System Mode:
ZONE 1
Zone LV
60 (clg)
Zone Size
.30
Weighted LV
18
Cooling Sum
Heating Sum
System Mode

8.3.2 Capacity request (System LV)

System LV is used to determine how much capacity will
be requested. System LV is determined by the zone with
largest load value in the current mode of operation. See
Section 6.2 Load Value for heating and cooling tables for
additional information regarding the load value ranges for
different systems.
Example for determining System Load Value:
ZONE 1
Zone LV
60 (clg)
System LV
For VSPD outdoor units and modulating furnaces the
System LV is scaled:
SysLV ≤ 80 = Raw LV x 1.25
SysLV > 80 = (Raw LV x .8333) + 33.33
Zone LV is not scaled, only System LV
Example for determining Scaled System Load Value:
ZONE 1 ZONE 2 ZONE 3 ZONE 4
Zone LV
60 (clg)
System LV
Scaled System LV
When zoning is applied the System LV may be inhibited for
the following reasons:
The sum of the calling zones is less than or equal to the
current stage of capacity (compressor and gas furnace
operation only)
(VSPD systems only) Auxiliary Heat Clamp is enabled
and the sum of the calling zones is less than or equal
to the clamp setting (Installer Settings>Clamp LV for
Auxiliary Heat)
For VSPD systems the speed of the compressor will be
limited based on the air flow capacity of the calling zones.
Oil return or other protection algorithms may override this
clamp
24
ZONE 2
ZONE 3
ZONE 4
50 (clg)
60 (htg)
50 (htg)
.45
.30
22.5
12
40.5
44.5
Heating
ZONE 2
ZONE 3
ZONE 4
50 (clg)
80 (clg)
50 (clg)
80
50 (clg)
80 (clg)
50 (clg)
80
System LV (80) x 1.25 = 100

8.3.3 Damper position

The position of the modulating dampers is determined by
the amount of capacity each zone is requesting.
The damper position for each same mode calling zone
.65
follows the calculation below:
32.5
Zone LV/ System LV = damper position
The minimum opening position is always 25% to reduce air
whistling from a partially opened damper
Zones in the opposite or "off" mode are closed unless the
system has calculated excess air.
Example of how Damper Positions are calculated for non-
VSPD and VSPD systems:
NON-VSPD
Zone LV
System LV
Damper Position
For non-VSPD systems one damper will always be full open
on a call for capacity and the other dampers will modulate
based on their load value.
VSPD
Zone LV
System LV
Scaled System LV
Damper Position
For VSPD cooling or compressor heating the scaling of
the system load value will result in the dampers being in
a less open position than non-VSPD systems. This partial
restriction helps maintain static pressure for improved air
flow distribution.

8.3.4 excess Air Management

The 1050 Control manages excess air without the need
for bypass dampers, dump zones or position stops in the
supply dampers.
The first method of managing excess air is to eliminate or
reduce the excess through equipment stage control and air
flow modulation
Equipment Stage Control – For systems with capacity
control, the 1050 Control will limit the capacity request
based on the sum of the calling zones size...insert chart
For systems with capacity control, if the sum of the
calling zones sizes are less than or equal to the
current stage of capacity the system load value will
be inhibited disallowing the next stage of operation
For VSPD systems, the speed of the compressor
will be limited based on air flow capabilities of the
calling zones. This inhibit may be overridden during
oil return mode or if the sum of the calling zones
is less than the minimum compressor speed at the
current outdoor conditions.
ZONE 1 ZONE 2 ZONE 3 ZONE 4
60 (clg)
50 (clg)
40 (clg)
60
100%
83%
67%
ZONE 1 ZONE 2 ZONE 3 ZONE 4
60 (clg)
50 (clg)
40 (clg)
60
Sytem LV (60) x 1.25 = 75
80%
67%
53%
18-HD80D1-6E-EN
50 (clg)
83%
50 (clg)
67%

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Comfortlink ii xl1050Tzon1050ac52zc

Table of Contents