Dimensioned Drawings; I A Water Connections - Mitsubishi Electric CLIMAVENETA BRAN2 0021M Installation, User And Maintenance Manual

Air/water chillers and heat pumps
Table of Contents

Advertisement

DIMENSIONED DRAWINGS

W1
=
E
W4
A
Dimension
A
B
C
D
E
Weight distribution BRAT2
W1
W2
W3
W4
Total in operation
Weight distribution BRAN2
W1
W2
W3
W4
Total in operation
WATER CONNECTIONS
The choice and installation of components is the responsibil-
ity of the installer who should follow good working practice
and current legislation. Construction of a bypass is recom-
mended to enable the pipes to be washed through without
having to disconnect the unit (see drain valves).
The connection piping should be supported in such a way
as to avoid it weighing on the unit.
The following devices must be installed on the water circuit:
1. Two pressure gauges with a suitable scale (intake and
outlet);
2. Two vibration damper joints (intake and outlet);
3. Two shut off valves (normal in intake and calibrating in out-
let);
4. A flow switch on the unit outlet to the system circuit
(compulsory). The flow switch must be calibrated by
the installer to a value equal to 70% of rated flow.
5. Two thermometers (intake and outlet).
6. An intake filter must be installed as close as possible
to the evaporator and positioned to allow easy
access for routine maintenance. 500 micron filter
mesh.
7. All the pipes must be insulated with suitable material to
prevent the formation of condensate and heat loss. The
insulating material must be a vapour barrier. Make sure
that the control and shut-off devices protrude from the
insulation.
6
BRAT2 - BRAN2 EN
C
W2
=
B
W3
D
0021M-T 0025M-T 0031M-T 0041M-T 0051T
mm
900
900
mm
640
940
mm
370
370
mm
320
320
mm
580
580
0021M-T 0025M-T 0031M-T 0041M-T 0051T
kg
33
39
kg
12
14
kg
11
13
kg
29
34
kg
85
100
0021M-T 0025M-T 0031M-T 0041M-T 0051T
kg
37
43
kg
13
15
kg
13
15
kg
32
37
kg
95
110
600
0061T
900
900
900
940
1240
1240
370
370
370
320
320
320
580
580
580
0061T
41
49
57
14
18
20
14
16
19
36
42
49
105
125
145
0061T
45
55
62
16
20
23
15
17
21
39
48
54
115
140
160
8. At the lowest points in the system, install drain valves for
easy emptying.
9. At the highest points in the system, install automatic or
manual air vent valves.
Failure to install the flow switch will mean the heat exchang-
er is not protected in the event of no flow of liquid.
Climaveneta cannot be held liable for any damage to the
unit and/or the system following the failure to install these
devices or the filter.
The correct operation of the components that help ensure
the safety of the appliance and the system should be
checked regularly.
Specifically, this involves cleaning the filters and checking
the operation of the flow switches installed.
Water flow to the chiller unit must conform to the values
shown in the section on "General Technical Data".
The flow of water must be maintained constant during oper-
ation.
The water content of the unit must be such as to avoid dis-
turbing operation of the refrigerant circuits.
400
0071T
0091T
900
1450
1450
1390
1200
1200
420
550
550
370
497
497
580
1477
1477
0071T
0091T
60
83
84
22
42
43
20
39
40
53
81
83
155
245
250
0071T
0091T
66
92
93
24
43
44
22
40
41
58
90
92
170
265
270
I
0101T
0121T
1450
1450
1700
1700
550
550
497
497
1477
1477
0101T
0121T
110
111
54
55
51
52
105
107
320
325
0101T
0121T
119
120
55
56
52
53
114
116
340
345