OPERATING LIMITS
50
45
40
35
30
25
20
15
10
5
0
-5
-10
-15
-15
-10
Operating range in COOLING
Water temperature head min-max= 3-8 K
Water circuit pressure min-max= 1-6 bars
Max storage temperature= 63°C
Maximum percentage of glycol= 40%
As standard, the unit is manufactured with operating parameters allowing water produced at the evaporator down to +5°C. If needing to produce
water down to -10°C, contact technical service.
60
55
50
45
40
35
30
25
20
-15
-10
-5
Operating range in heating
Water temperature head min-max= 4-10 K
Water circuit pressure min-max= 1-6 bars
Maximum water temperature at system heat exchanger water inlet +50°C
Max storage temperature= 63°C
Maximum percentage of glycol= 40%
16
BRAT2 - BRAN2 EN
COOLING
OPERATION WITH
WATER-GLYCOL MIX
-5
0
Water outlet temperature at evaporator [°C]
HEATING
0
5
10
15
Outside air temperature [°C]
5
10
20
25
30
35
U I A
15
20
40
45
50