Diagnosing and troubleshooting

10.1

Communication troubleshooting

1. Check the following:
– There is power at the device.
– The LCD shows the relevant data.
– The device can be programmed using the handheld programmer.
– If any fault codes are being displayed see General Fault Codes (Page 169) for a
2. Verify that the wiring connections are correct.
3. See the table below for specific symptoms.
Symptom
The device cannot be programmed via the
handheld programmer.
You try to set a SITRANS LR250 parame-
ter via remote communications but the
parameter remains unchanged.
If you continue to experience problems go to our website and check the FAQs for SITRANS
LR250:
Product page (http://www.siemens.com/LR250), or contact your Siemens representative.
10.2

Device status icons

Icon
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG
detailed list.
Priority
Meaning
Level
1
Maintenance alarm
Measurement values are not valid
2
Maintenance warning: maintenance demanded immediately
Measured signal still valid
Corrective action
Ensure Write Protect (6.2.1.) is set to the unlock
value.
Ensure Write Protect (6.2.1.) is set to the unlock
value, then try setting the parameter via the handheld
programmer.
Ensure Access Control (6.1.1.) is set to Read/ Write.
Some parameters can be changed only when the
device is not scanning. Try pressing Mode
the device into PROGRAM mode.
10
to put
167