Oil Venting Requirements, continued
1

Oil Venting System

Positive pressure venting:
Boiler, breeching and vent operate at positive
pressure The entire engineered vent system must
be rated for positive pressure venting Ensure 0 1"
2
positive pressure at test opening The minimum
vent height is 3 feet above roof or snow line, and in
accordance to local codes that have jurisdiction See
Figure 38
Natural draft or negative pressure venting:
3
Boiler operates with positive pressure overfire.
Chimney may provide excess draft, which may
require the installation of a draft control device to
minimize draft in accordance to local codes that have
jurisdiction The control must be set to maintain 0 1"
positive pressure at the flue collar. The minimum
4
vent height is 3 feet above roof or snow line, and in
accordance to local codes that have jurisdiction See
Figure 39 and Figure 40