GFK-2573AB
Version
IC695PNC001-AK
IC695PNC001-AJ
IC695PNC001-AH
IC695PNC001-AG
IC695PNC001-AF
IC695PNC001-AE
IC695PNC001-AD
IC695PNC001-AC
IC695PNC001-AB
IC695PNC001-AA
®
HART
is a registered trademark of the HART Communication Foundation of Austin, Texas USA. Any use of the term HART hereafter in this document, or any
document referenced by this document, implies the registered trademark.
Firmwar
Date
e
Revision
Added support for HART
PROFINET. A HART-capable PROFINET scanner
May
(IC695PNS001 or IC695CEP001) must also be employed to
2.20
support the HART-capable RX3i analog modules over
2015
PROFINET. The CPU used in the application must also contain
firmware that supports HART Pass-Through.
Increased number of PROFINET Devices that PNC001 can
control from 64 to 128. Still limited to 63 devices in an MRP
Ring if the PNC001 is the MRP Ring Manager.
Added new SFP OK status bits to existing PNC001 status
Feb
2.11
dword.
2015
Introduced new Critical Network Port diagnostic fault
configuration and logging. Configuring ports as critical also
forces Copper ports to 100 Mbps.
Jun
Adds support for COMMREQs required by the Genius
2.05
2014
Communication Gateway (GCG001) module.
Adds remote PROFINET IO to PACSystems RX3i Hot Standby
Dec
Redundancy systems. Also adds MRP status bits.
2.00
2013
For details, see New Features and Enhancements below.
Corrects issue storing PROFINET device configuration greater
Aug
than 64K bytes in size.
1.23
2013
For details, see RX3i PROFINET Controller IPI, GFK-2573F.
Jul
Corrects an issue where, in some configurations, the PNC001
1.22
2013
entered a mode that caused it to repeatedly power up.
Addresses a power-up issue affecting the following revisions
IC695PNC001-AB and IC695PNC001-AC.
Jul
1.21
Although no units that exhibited this issue were shipped, it is
2012
recommended to update the firmware to prevent the
possibility of encountering a power-up issue in the field.
Mar
Adds support for up to 255 PROFINET IO Devices per RX3i
1.20
2012
CPU.
Adds support for SNMP and LLDP standards to facilitate
network management.
Dec
1.10
2011
Provides enhanced Revision Information in the Explore
PROFINET Networks tool.
Initial release.
Jun
1.00
2011
Supports GSDML Version 2.2 and earlier.
Comments
®
Pass-Through feature set over
Jul 2022