Lochinvar EcoCharger ECH 32-220 G CE Installation, Commissioning, User & Maintenance Instructions page 99

Gas fired condensing water heater
Table of Contents

Advertisement

Description
General
Contents
Empty Weight
Maximum floor load
Maximum operating pressure
(vented)
Maximum operating pressure
(unvented)
Control thermostat -
adjustment range
Control thermostat -
default value
Hysteresis upwards -
adjustment range
Hysteresis upwards -
default value
Hysteresis downwards -
adjustment range
Hysteresis downwards -
default value
Number of (electrical) anodes -
Observed pressure differential
across the pressure switch
Pressure differential to open
the pressure switch
Heating time ΔT = 45 °C
Electrical
Electrical power consumption
Supply voltage
(-15%, +10% VAC)
Mains frequency (± 1Hz)
IP class
0311723_ECH_32-129_III_ENEN_V2.6, 2022-10-17
Unit
ECH 87-480
litres
488
kg
405
kg
893
kPa (bar)
800 (8)
kPa (bar)
550 (5.5)
°C
40...80
°C
65
°C
0...5
°C
5
°C
0...10
°C
5
2
Pa
³ 260
Pa
< 210
min.
18
W
95
volts
230
Hz
50
-
IP 20
ECH 106-480
ECH 129-480
488
488
405
405
893
893
800 (8)
800 (8)
550 (5.5)
550 (5.5)
40...80
40...80
65
65
0...5
0...5
5
5
0...10
0...10
5
5
2
2
³ 260
³ 260
< 210
< 210
15
12
145
240
230
230
50
50
IP 20
IP 20
99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents